6.4.1
Signal limits
Table 6-1: Maintenance Channels' Limits
Channel
Short range
Medium range
Long range
17 ft.
(5 m)
52 ft.
(16 m)
46 ft.
(14 m)
131 ft.
(40 m)
197 ft.
(60 m)
Reference
2 V
gain 0
1.5 V
gain 2
2 V
gain 0
1 V
gain 1
1 V
gain 2
Signal 1 & 2
2 V
gain 0
1.5 V
gain 2
2 V
gain 0
1 V
gain 1
1 V
gain 2
Ratio 1 & 2
0.6 to 1.4
NQRat 1 & 2
0.97 to 1.03
ppm.m
0 ppm.m
Temperature
Up to 25 °C beyond ambient temperature
Voltage
32 Vdc > V > 18 Vdc
(1)
The minimum distance, as defined on the model number.
(2)
Half the maximum distance, as defined on the model number.
(3)
The maximum distance, as defined on the model number.
Reference Manual
Operation
00809-0100-4036
October 2021
Rosemount 936
53
Содержание Rosemount 936
Страница 1: ...Reference Manual 00809 0100 4036 Rev AD October 2021 Rosemount 936 Toxic Open Path Gas Detector ...
Страница 4: ...4 ...
Страница 8: ...Product overview Reference Manual October 2021 00809 0100 4036 8 Emerson com Rosemount ...
Страница 24: ...Operating modes Reference Manual October 2021 00809 0100 4036 24 Emerson com Rosemount ...
Страница 30: ...Specifications Reference Manual October 2021 00809 0100 4036 30 Emerson com Rosemount ...
Страница 50: ...Installation Reference Manual October 2021 00809 0100 4036 50 Emerson com Rosemount ...
Страница 68: ...Wiring configurations Reference Manual October 2021 00809 0100 4036 68 Emerson com Rosemount ...
Страница 72: ...Support Reference Manual October 2021 00809 0100 4036 72 Emerson com Rosemount ...
Страница 74: ...Short range model Reference Manual October 2021 00809 0100 4036 74 Emerson com Rosemount ...