53
Reference Manual
00809-0100-4772, Rev FA
March 2016
4.2.2
Diagnostics
In addition to the BLOCK_ERR and XD_ERROR parameters, more detailed information on
the measurement status can be obtained through the TB_ELECTRONICS_STATUS.
lists the potential errors and the possible corrective actions for the given values.
Table 4-3. XD_ERR Conditions
Condition
number
Condition name and description
15
Out of Service: The actual mode is out of service.
16
Unspecified error: An unidentified error occurred.
17
General Error: A general error that cannot be specified below
occurred.
18
Calibration Error: An error occurred during calibration of the device,
or a calibration error was detected during normal operations.
19
Configuration Error: An error occurred during configuration of the
device, or a configuration error was detected during normal
operations.
20
Electronics Failure: An electrical component failed.
21
Mechanical Failure: A mechanical component failed.
22
I/O Failure: An I/O failure occurred.
23
Data Integrity Error: Data stored in the device are no longer valid
due to a nonvolatile memory checksum failure, a data verify after
write failure, etc.
24
Software Error: The software has detected an error due to an
improper interrupt service routine, an arithmetic overflow, a
watchdog time-out, etc.
25
Algorithm Error: The algorithm used in the transducer block
produced an error due to overflow, data reasonableness failure, etc.
Table 4-4. Transducer Block Status Definitions (TB_ELECTRONICS_STATUS)
Value
Name and description
LCD display
indication
(if any)
Corrective actions
0x00000002
SW_DETECTED_ERR: The device software has detected
a software (typically math) error.
FAULT SFTWR
Restart the transmitter.
(1)
0x00000004
COPROCESSOR_ERR: The coprocessor has detected a
math or instruction error.
FAULT COPRO
Restart the transmitter.
0x00000010
INTERRUPT_ERROR: The transducer block has detected
that the coprocessor ASIC has stopped generating flow
data interrupts.
FAULT ASIC
Restart the transmitter.
0x00000020
COPROC_RAM_ERR: The coprocessor has detected a
RAM error at startup.
FAULT RAM
Restart the transmitter.
0x00000040
COPROC_ROM_ERR: The coprocessor has detected a
ROM error at startup.
FAULT ROM
Restart the transmitter.