40
Reference Manual
00809-0100-4697, Rev GA
Section 3: Configuration
November 2014
Configuration
3.4.6
Recommended actions for field diagnostics alerts
RECOMMENDED_ACTION
The RECOMMENDED_ACTION parameter displays a text string that will give a recommended
course of action to take based on which type and which specific event of the Field Diagnostics
alerts are active.
Table 3-12. RB.RECOMMENDED_ACTION
Alarm type
Active event
Recommended action
None
None
No action required
Failed
ASIC Failure
ASIC Failure has occurred. Restart the transmitter. If condition
persists, replace the transmitter
Failed
Electronics Failure
Electronics Failure has occurred. Restart the transmitter. If
condition persists, replace the transmitter.
Failed
Hardware/Software
Incompatible
Contact a Service Center and verify the Device Information
(RESOURCE.HARDWARE_REV and
RESOURCE.RB_SFTWR_REV)
Failed
Memory Failure
Restart the transmitter by writing the RESTART parameter to
4 - Restart Processor. If condition persists, replace the
transmitter.
Failed
Body Temperature
Failure
Verify the ambient temperature is within the operating limits
of this device. If condition persists, replace the device
Failed
Sensor 1 Failure
Verify the Instrument process for Sensor 1 is within the Sensor
range and/or confirm sensor configuration and wiring.
Failed
Sensor 2 Failure
Verify the Instrument process for Sensor 2 is within the Sensor
range and/or confirm sensor configuration and wiring.
Failed
Sensor 3 Failure
Verify the Instrument process for Sensor 3 is within the Sensor
range and/or confirm sensor configuration and wiring.
Failed
Sensor 4 Failure
Verify the Instrument process for Sensor 4 is within the Sensor
range and/or confirm sensor configuration and wiring.
Failed
Sensor 5 Failure
Verify the Instrument process for Sensor 5 is within the Sensor
range and/or confirm sensor configuration and wiring.
Failed
Sensor 6 Failure
Verify the Instrument process for Sensor 6 is within the Sensor
range and/or confirm sensor configuration and wiring.
Failed
Sensor 7 Failure
Verify the Instrument process for Sensor 7 is within the Sensor
range and/or confirm sensor configuration and wiring.
Failed
Sensor 8 Failure
Verify the Instrument process for Sensor 8 is within the Sensor
range and/or confirm sensor configuration and wiring.
Off Spec
CJC Degraded
If T/C sensors are being used, restart the device. If condition
persists, replace the device.
Off Spec
Body Temperature
Out of Range
Verify the ambient temperature is within operating limits
Off Spec
Sensor 1 Degraded
Confirm the operating range of Sensor 1 and/or verify the
sensor connection and device environment.
Off Spec
Sensor 2 Degraded
Confirm the operating range of Sensor 2 and/or verify the
sensor connection and device environment.
Off Spec
Sensor 3 Degraded
Confirm the operating range of Sensor 3 and/or verify the
sensor connection and device environment.
Содержание Rosemount 848T
Страница 2: ......
Страница 4: ...ii Reference Manual 00809 0100 4697 Rev GA Title Page November 2014 ...
Страница 12: ...4 Reference Manual 00809 0100 4697 Rev GA Section 1 Introduction November 2014 Introduction ...
Страница 26: ...18 Reference Manual 00809 0100 4697 Rev GA Section 2 Installation November 2014 Installation ...
Страница 60: ...52 Reference Manual 00809 0100 4697 Rev GA Section 3 Configuration November 2014 Configuration ...
Страница 130: ...120 Reference Manual 00809 0100 4697 Rev GA Appendix D Function Blocks November 2014 Function Blocks ...
Страница 134: ...Index 4 Reference Manual 00809 0100 4697 Rev GA Index November 2014 Index ...
Страница 135: ......