39
Reference Manual
00809-0200-4702, Rev CA
Section 5: Operation and Maintenance: Models 702DX22 and 702DX61
February 2013
Operation and Maintenance: Models 702DX22 and 702DX61
5.2.3
Liquid Hydrocarbon Detection, Measurement Option Code
61 (702DX61)
Figure 5-5. Fuel Sensor Terminal
The Liquid Hydrocarbon Detection configuration is intended for use with the Tyco
®
TraceTek
®
Fast Fuel Sensor, or TraceTek sensing cable.
Figure 5-6. Fuel Sensor Connection
Connecting the transmitter to the fast fuel sensor and TraceTek
sensing cable
The connections to the Fast Fuel Sensor TraceTek sensing cable are made by matching the
appropriately colored wires to the matching colored termination lugs.
The Rosemount 702 Wireless Discrete Transmitter can support up to 3 Fast Fuel
sensors. These Fast Fuel sensors are connected using TraceTek Modular Leader Cable
(TT-MLC-MC-BLK), optional modular jumper cables (TT-MJC-xx-MC-BLK) and branching
connectors (TT-ZBC-MC-BLK) as suggested in
Figure 3-11 on page 25
.
Содержание Rosemount 702 Series