Calibrate
Prerequisites
Ensure that there is no liquid above the calibration ring
at the end of the still-pipe when
calibrating the gauge. Then the calibration ring is the only object that will be detected by
the gauge. The product level presented by the Rosemount 5900S will be equal to the
position of the calibration ring measured from the Zero Level near the bottom of the tank.
Procedure
1. Check the distance measured by the Rosemount 5900S from the Gauge Reference
to the calibration ring.
This is referred to as the Ullage
value defined by: Ullage = R - L, where
•
R
is the tank height measured from the Tank Reference Point to the Zero Level.
For LPG tanks the calibration ring is used as Zero Level and the Tank Reference
Point is equal to the Gauge Reference Point.
•
L
is the product level measured from the Zero Level.
If the Ullage value is not equal to the actual distance between the
Gauge Reference
Point
and the calibration ring, you will need to adjust the
Calibration Distance
parameter.
2. Right-click the device icon and select the
Properties
→
Geometry
tab.
(10)
See
.
(11)
See
Reference Manual
Configuration
00809-0100-5900
September 2019
Rosemount 5900S Radar Level Gauge
121
Содержание Rosemount 5900S Series
Страница 1: ...Reference Manual 00809 0100 5900 Rev EA September 2019 Rosemount 5900S Radar Level Gauge ...
Страница 6: ...Contents Reference Manual September 2019 00809 0100 5900 vi Reference Manual ...
Страница 12: ...Introduction Reference Manual September 2019 00809 0100 5900 12 Reference Manual ...
Страница 182: ...Configuration Reference Manual September 2019 00809 0100 5900 182 Reference Manual ...
Страница 186: ...Operation Reference Manual September 2019 00809 0100 5900 186 Reference Manual ...
Страница 222: ...Service and troubleshooting Reference Manual September 2019 00809 0100 5900 222 Reference Manual ...
Страница 266: ...Product Certifications Reference Manual September 2019 00809 0100 5900 266 Reference Manual ...