68
Reference Manual
00809-0100-4024, Rev CA
Configuration
March 2020
Configuration
4.5
Analog output
The Rosemount 5600 has the possibility to handle two analog outputs which can be separately
configured.
However, if your transmitter is equipped with a primary 4-20 mA HART output, you must use Analog
Output 1. (Analog Output 1 is not available for primary output when using other bus communication
protocols than HART).
illustrates how the analog output signal is related to the actual measured product level and
the specified upper and lower limits. As illustrated, if the source signal exceeds the Upper limit or falls
below the Lower limit, the output current is set according to the specified Alarm Mode settings.
If your transmitter is equipped with an optional analog output
(Analog Output 2), configure it as described above.
Output Source
Select the source to control the analog output.
Upper Range Value
Lower Range Value
Enter the range values that correspond to the analog output values 4 and 20 mA. You
can specify any values as long as the Upper Range Value is above the Lower Range
Value. If the measured value goes beyond the measurement range, the transmitter
enters the alarm mode.
Alarm Mode
Choose the desired Alarm Mode. The Alarm Mode specifies the analog output state
when a measurement error occurs or when the measured value is out of range.
High: the output current is set to 22 mA.
Low: the output current is set to 3.8 mA.
Freeze Current: the output current is set to the present value at the time when the
error occurs.
Binary High: the output current is 4 mA under normal conditions. If there is a
measurement error, or when the source signal is out of range, the output current is set
to 20 mA.
Binary Low: the output current is 20 mA under normal conditions. If there is a
measurement error, or when the source signal is out of range, the output current is set
to 4 mA.
Disable Limit Alarm if
Out of Range
If the detected limit is out side the upper or lower limit, setting this parameter
suppresses the analog output from going into alarm mode.
Содержание Rosemount 5600 Series
Страница 2: ......
Страница 4: ...4 Reference Manual 00809 0100 4024 Rev CA Title Page March 2020 Title Page ...
Страница 16: ...16 Reference Manual 00809 0100 4024 Rev CA Introduction March 2020 Introduction ...
Страница 54: ...54 Reference Manual 00809 0100 4024 Rev CA Mechanical Installation March 2020 Mechanical Installation ...
Страница 119: ...Product Certifications 119 Product Certifications March 2020 Reference Manual 00809 0100 4024 Rev CA ...
Страница 122: ...Product Certifications March 2020 Reference Manual 00809 0100 4024 Rev CA Product Certifications 122 ...
Страница 125: ...125 Reference Manual 00809 0100 4024 Rev CA Index March 2020 Index Strapping Table 71 ...
Страница 126: ...126 Reference Manual 00809 0100 4024 Rev CA Index March 2020 Index ...
Страница 127: ......