12
Reference Manual
00809-0100-4022, Rev GA
Configuration
September 2016
Configuration
AMS Device Manger
Right click on the device and select
Configuration Properties
from the menu.
1.
In the
Basic Setup
tab, enter the damping value in the
Damp
field, select
Apply
.
2.
An
Apply Parameter Modification
screen appears, enter desired information and
select
OK
.
3.
After carefully reading the warning provided, select
OK
.
2.8
Detailed setup
2.8.1
Failure mode alarm and saturation
The Rosemount 4600 Transmitter automatically and continuously perform self-diagnostic
routines. If the self-diagnostic routines detect a failure, the transmitter drives the output to
configured alarm values. The transmitter will also drive the output to configured saturation
values if the applied pressure goes outside the 4-20 mA range values.
Note
The failure mode alarm direction can also be configured using the Field Communicator or
AMS Device Manager.
Note
Under some failure conditions, the transmitter will ignore user configured alarm conditions
and drive the transmitter to low alarm.
The Rosemount 4600 Transmitter have three configurable options for failure mode alarm
and saturation levels:
Rosemount (Standard), see
Custom, see
Table 2-1. Rosemount (Standard) Alarm and Saturation Values
Level
4–20 mA saturation
4–20 mA alarm
Low
3.9 mA
≤
3.75 mA
High
20.8 mA
≥
21.75 mA
Table 2-2. Custom Alarm and Saturation Values
Level
4–20 mA saturation
4–20 mA alarm
Low
3.7 mA — 3.9 mA
3.6 mA — 3.8 mA
High
20.1 mA — 21.5 mA
20.2 mA — 23.0 mA