HART Functionality
3-13
Loop test
is used to set the output of the device at a
specified analog value, and may be used to test the
integrity of the loop and the operation of indicators,
recorders, or similar devices in the loop.
Calibration
is used to perform such operations as
performing a sensor trim, D/A trim, and scaled D/A trim.
Basic setup
The Basic setup menu provides quick access to a
number of configurable parameters including tag, unit,
range values, and damping.
The options available in the Basic setup menu are the
most fundamental tasks that can be performed with a
device. These tasks are a subset of the options available
under the Detailed setup menu.
The
Tag
alphanumeric identifies a specific device.
Changing the unit option affects the engineering units
that are displayed. Changing range values changes the
analog output scaling. Changing damping affects the
response time of the transmitter and is often used to
smooth the output when there are rapid input variations.
Detailed setup
The Detailed setup menu provides access to every
editable device parameter and all device functions. The
Detailed setup menu varies from one HART device to
another. Functions in this menu can include
characterization, configuration, and sensor and output
trims.
Review
The Review menu lists all of the static parameters read
from the connected device, including information about
the device and sensor setup and limitations. It also
includes information about the connected device such as
tag, materials of construction, and device software
revision.
Содержание Rosemount 375
Страница 1: ...USER S MANUAL 375 Field Communicator User s Manual ...
Страница 2: ......
Страница 4: ......
Страница 10: ...Introduction 1 2 ...
Страница 40: ...Learning the Basics 2 30 ...
Страница 112: ...Product Certifications B 8 ...
Страница 113: ...Product Certifications B 9 ...
Страница 114: ...Product Certifications B 10 ...
Страница 132: ...G viii ...