![Emerson Rosemount 3490 Series Скачать руководство пользователя страница 123](http://html.mh-extra.com/html/emerson/rosemount-3490-series/rosemount-3490-series_reference-manual_2400788123.webp)
Related information
Set-up the relays
Set-up the current output
Control unit reporting of alarms and faults
Table 4-30: Control Unit Reporting of Alarms
Source
Cause
As seen on
screen
Status
LED
Full PV
display
Relay
output
Current
output
Alarm
report
(D830)
Fault
report
(D831)
3490
Current Output reached
linear limit
mA o/p Sat
N/A
N/A
Yes
Yes
Yes
N/A
Logging memory almost
full
Lg Mem Filling
N/A
N/A
Yes
Yes
Yes
N/A
Logging memory is full
Log Mem Full
N/A
N/A
N/A
Yes
Yes
N/A
Digital Input 1 active
Digital In 1
N/A
N/A
Yes
Yes
Yes
N/A
Digital Input 2 active
Digital In 2
N/A
N/A
Yes
Yes
Yes
N/A
Alarm suppressed by
digital input
Alarm
Suppressed
N/A
N/A
N/A
N/A
Yes
N/A
Custom relay operation
retries exceeded
Max Retries
N/A
N/A
Yes
Yes
Yes
N/A
Current input below lower
linear limit
mA In Low
N/A
N/A
Yes
Yes
Yes
N/A
Current input above
higher linear limit
mA In High
N/A
N/A
Yes
Yes
Yes
N/A
Raising level despite
relays on
Rising Level
N/A
N/A
Yes
Yes
Yes
N/A
Relay number of
operations exceeded
Relay Operations N/A
N/A
Yes
Yes
Yes
N/A
Relay run-time exceeded
Relay Runtime
N/A
N/A
Yes
Yes
Yes
N/A
Pump efficiency below
limit
Pump Efficiency
N/A
N/A
Yes
Yes
Yes
N/A
No activity of Control
Relay
No activity
N/A
N/A
Yes
Yes
Yes
N/A
Xmtr
Transmitter PV out-of-
limits
PV OL
N/A
N/A
N/A
Yes
Yes
N/A
(1)
The pump efficiency feature is on Rosemount 3491 and 3492 control units.
Reference Manual
Getting started
00809-0100-4841
January 2021
Emerson.com/Rosemount
123
Содержание Rosemount 3490 Series
Страница 4: ...4 ...
Страница 8: ...Introduction Reference Manual January 2021 00809 0100 4841 8 Emerson com Rosemount ...
Страница 16: ...Control unit overview Reference Manual January 2021 00809 0100 4841 16 Emerson com Rosemount ...
Страница 36: ...Installation Reference Manual January 2021 00809 0100 4841 36 Emerson com Rosemount ...
Страница 134: ...Getting started Reference Manual January 2021 00809 0100 4841 134 Emerson com Rosemount ...
Страница 158: ...Specifications and reference data Reference Manual January 2021 00809 0100 4841 158 Emerson com Rosemount ...
Страница 184: ...Additional features Reference Manual January 2021 00809 0100 4841 184 Emerson com Rosemount ...
Страница 189: ...Reference Manual 00809 0100 4841 January 2021 Emerson com Rosemount 189 ...