Table 4-21: Custom Mode Relay Parameters
Parameter
Description
Factory default
P250
Start On
Relay energizes when the selected condition is true.
See also
.
None
P251
Stop On
Relay de-energizes when the selected condition is
true. See also
None
P252
Stop If
Relay de-energizes when the selected condition is
true. See also
. P252 is a fail-safe for P251.
None
P253
Start Time
This defines the clock time for when a Custom mode
relay operation will begin (if P250 = Time) or end (if
P251 = Time).
“7:00” - i.e. 7AM
P254
Interval
This is for defining the interval for repeating a
Custom mode relay operation.
P255 and P256 are for setting up a second starting
time and an associated interval.
“1:00” i.e. 1hr
0min
P257
Max Retries
This defines the maximum number of failed
attempts to perform Custom mode relay operations
before it is deemed an alarm condition.
The alarm condition can happen if the control unit is
in Program mode, which prevents all Custom mode
relay operations from starting. Also, it can happen
when the maximum time for an energized relay has
been reached and is preventing a Custom mode
relay operation from completing.
10
Table 4-22: P250/P251/P252 Options
Options
Purpose of option
Start on
(P250)
Stop on
(P251)
Stop if
(P252)
None
Switched off.
Yes
Yes
Yes
Time
P253 and P254 determine when a Custom
mode relay is to be energized.
Yes
Yes
N/A
PV > Level
Energize a Custom mode relay when the
control unit PV value (D800) is greater
than the relay On Point.
Yes
N/A
N/A
PV < Level
De-energize a Custom mode relay when
the control unit PV value (D800) less than
the relay On point.
N/A
Yes
Yes
Energize a Custom mode relay when a
digital input is active.
Yes
Yes
Yes
When a Digital Input is active, de-energize
a Custom mode relay after X seconds
delay.
N/A
N/A
Yes
(1)
This does not require Digital Input IN1 or IN2 to be allocated an action.
(2)
Abbreviations: “Ext Trig” = External Trigger (Digital Input).
Reference Manual
Getting started
00809-0100-4841
January 2021
Emerson.com/Rosemount
115
Содержание Rosemount 3490 Series
Страница 4: ...4 ...
Страница 8: ...Introduction Reference Manual January 2021 00809 0100 4841 8 Emerson com Rosemount ...
Страница 16: ...Control unit overview Reference Manual January 2021 00809 0100 4841 16 Emerson com Rosemount ...
Страница 36: ...Installation Reference Manual January 2021 00809 0100 4841 36 Emerson com Rosemount ...
Страница 134: ...Getting started Reference Manual January 2021 00809 0100 4841 134 Emerson com Rosemount ...
Страница 158: ...Specifications and reference data Reference Manual January 2021 00809 0100 4841 158 Emerson com Rosemount ...
Страница 184: ...Additional features Reference Manual January 2021 00809 0100 4841 184 Emerson com Rosemount ...
Страница 189: ...Reference Manual 00809 0100 4841 January 2021 Emerson com Rosemount 189 ...