4.3.7
Setting 4 mA and 20 mA levels using ranging (on the 3101)
Screen display:
S--4 and S-20
Note
If the 4 and 20 mA levels are already programmed, as described in the section
Lost Echo action (on the 3101)” on page 31
, this menu option must be skipped; it overwrites
previously entered data for them. Press the green button
to get to the final menu option, “Lrn”
This is for setting the 4 mA or 20 mA levels by ranging the instrument to a known target,
e.g. the present level in a vessel.
To change the 4 mA level
1.
If entering the menu system from the PV display, press the green button
repeatedly
until the “S--4” menu option is indicated (see above note).
2.
Ensure the target is the 4 mA level and, with the display indicating that level, press the
blue button
.
3.
The display indicates the present 4 mA level setting, not the new level reading.
If this setting is correct, press the red button
and then the green button
to get to
the next menu option. Otherwise, continue with step (
).
4.
Press the blue button
. The display flashes alternately “4” and the new level reading.
5.
Press the blue button
to confirm the new level reading is the new 4 mA level.
6.
Press the red button
to save if the new 4 mA level is correct, or press the blue
button
to not save. Afterwards, depending on the button pressed, either the “S--4”
menu or the next menu appears.
Note
for a map of the programming menu structure and how to access all
the menu options.
To change the 20 mA level
1.
If entering the menu system from the PV display, press the green button
repeatedly
until the “S-20” menu option is indicated (see the above note).
2.
Ensure the target is the 20 mA level and, with the display indicating that level, press the
blue button
.
3.
The display indicates the present 20 mA level setting, not the new level reading. If this
value is correct, press the red button
and then the green button
to get to the next
menu option. Otherwise, continue with step (
4.
Press the blue button
. The display flashes alternately “20” and the new level reading.
5.
Press the blue button
to confirm the new level reading is the new 20 mA level.
Содержание Rosemount 3101
Страница 2: ......
Страница 4: ...ii Reference Manual 00809 0100 4840 Rev CB Title Page February 2015 ...
Страница 12: ...x Reference Manual 00809 0100 4840 Rev CB Contents February 2015 Contents ...
Страница 34: ...22 Reference Manual 00809 0100 4840 Rev CB Section 3 Installation February 2015 Installation ...
Страница 68: ...56 Reference Manual 00809 0100 4840 Rev CB Section 4 Starting up February 2015 Starting up ...
Страница 112: ...100 Reference Manual 00809 0100 4840 Rev CB Appendix B Product Certifications February 2015 Product Certifications ...
Страница 120: ...108 Reference Manual 00809 0100 4840 Rev CB Appendix C Integrated Display Menus February 2015 Integrated Display Menus ...
Страница 128: ...116 Reference Manual 00809 0100 4840 Rev CB Appendix E Field Communicator Menus February 2015 Field Communicator Menus ...
Страница 236: ...224 Reference Manual 00809 0100 4840 Rev CB Index February 2015 Index ...
Страница 237: ......
Страница 238: ......
Страница 239: ......