Reference Manual
00809-0100-4840, Rev. BA
July 2008
F-13
Rosemount 3100 Series
P014
(Profile Height or Power)
P014 Description
When calculating the volume of liquid contents in an ideal horizontal cylinder
or sphere, P014 is set to the diameter, as shown by Figure F-4 on page F-9.
When calculating the volume of liquid contents or flow in an irregular shaped
vessel or open channel, P014 is set to the maximum height or flow rate, as
shown by Figure 14 and Figure 15 on page 16.
When calculating the rate of liquid flow in a standard open channel,
parameters P013 and P014 are terms in a flow rate calculation, as specified
for Flume/Weir options described for P011 (Tank Shape).
Minimum/Maximum value
0.0/999999
P015
(Upper Range Value)
P015 Description
This defines the Process Value (PV) represented by a 20 mA current output
from the transmitter.
The span of the 4–20 mA current output is defined by P015 and P016. It is not
necessary for P015 to have a value that is greater than P016, in which case
the current output will decrease for an increasing PV.
For example, consider a tank with the capacity for 120 gallons. When the tank
is the full, a 20 mA current output is required from the transmitter. Therefore,
P015 is set to 120 if the PV is being measured in gallons. P016 would
normally be set to 0.0 (gallons) for 4 mA current output to indicate an empty
tank.
Display (reported) units of measurement are as selected for the PV by P012.
Minimum/Maximum value
0.0/999999
P016
(Lower Range Value)
P016 Description
This defines the Process Value (PV) represented by a 4 mA current output
from the transmitter.
The span of the 4–20 mA current output is defined by P015 and P016. It is not
necessary for P015 to have a value that is less than P016, in which case, the
current output will decrease for an increasing PV.
For example, consider a tank with the capacity for 120 gallons. When the tank
is the empty, a 4 mA current output is required from the transmitter. P016 is
set to 0.0 if the PV is being measured in gallons. P015 would normally be set
to 120.0 (gallons) for 20 mA current output to indicate a full tank.
Display (reported) units of measurement are as selected for the PV by P012.
Minimum/Maximum value
0.0/999999
Содержание Rosemount 3100 Series
Страница 2: ......
Страница 4: ......
Страница 12: ...Reference Manual 00809 0100 4840 Rev BA July 2008 Rosemount 3100 Series 1 4 ...
Страница 16: ...Reference Manual 00809 0100 4840 Rev BA July 2008 Rosemount 3100 Series 2 4 ...
Страница 84: ...Reference Manual 00809 0100 4840 Rev BA July 2008 Rosemount 3100 Series A 10 ...
Страница 97: ...Reference Manual 00809 0100 4840 Rev BA July 2008 B 13 Rosemount 3100 Series Sheet 2 of 3 ...
Страница 98: ...Reference Manual 00809 0100 4840 Rev BA July 2008 Rosemount 3100 Series B 14 Sheet 3 of 3 ...
Страница 104: ...Reference Manual 00809 0100 4840 Rev BA July 2008 Rosemount 3100 Series C 6 ...
Страница 114: ...Reference Manual 00809 0100 4840 Rev BA July 2008 Rosemount 3100 Series E 6 ...
Страница 140: ...Reference Manual 00809 0100 4840 Rev BA July 2008 Rosemount 3100 Series F 26 ...
Страница 141: ......
Страница 142: ......
Страница 143: ......