Quick Installation Guide
00825-0100-4840, Rev AB
January 2008
Rosemount 3100 Series
21
Product Certifications
NOTE:
A safety isolator such as a zener barrier is needed for intrinsic safety.
Factory Mutual (FM) Approvals
(Models 3101/3102)
Factory Mutual (FM) Ordinary Location Approval
G5
Project ID: 3024095
The transmitter has been examined and tested to determine that
the design meets basic electrical, mechanical, and fire protection
requirements by FM, a nationally recognized testing laboratory
(NRTL) as accredited by the Federal Occupational Safety and
Health Administration (OSHA).
(Model 3105)
Factory Mutual (FM) Intrinsically Safe Approval
I5
Project ID: 3024095
Intrinsically Safe for Class I, Div. 1, Groups A, B, C and D
Intrinsically Safe for Class I, Zone 0, AEx ia IIC
Temperature Code: T4 at +60°C, max ambient
Temperature Code: T6 at +55°C, max ambient
Control Drawing: 71097/1216
Ui = 30 V, li = 120 mA, Pi = 0.82 W, Li = 108
P
H, Ci = 0 nF.
Factory Mutual (FM) Non-Incendive Approval
I5
Project ID: 3024095
Non-Incendive for Class I, Div. 2, Groups A, B, C and D
Non-Incendive for Class I, Zone 2, AEx nA IIC
Temperature Code: T4 at +60°C, max ambient
Temperature Code: T6 at +55°C, max ambient
Control Drawing: 71097/1216
Ui = 30 V, li = 120 mA, Pi = 0.82 W, Li = 108
P
H, Ci = 0 nF