Transmitter installation
Figure 2-1: Installation Flowchart
2.1
Mount the transmitter
Place the transmitter to the desired orientation before mounting.
Transmitter must not be securely mounted or clamped in place when
changing transmitter orientation.
Conduit entry orientation
When installing a Rosemount 3051HT, it is recommended installing so a
conduit entry faces downward or parallel to the ground to maximize
drainability when cleaning.
Environmental seal for housing
Thread sealing (PTFE) tape or paste on male threads of conduit is required to
provide a watertight/dustproof conduit seal and meets requirements of
NEMA
®
Type 4X, IP66, IP68, and IP69K. Consult factory if other Ingress
Protection ratings are required.
Note
IP69K rating only available on units with a SST housing and option code V9 in
the model string.
For M20 threads, install conduit plugs to full thread engagement or until
mechanical resistance is met.
In-line gauge transmitter orientation
The low side pressure port (atmospheric reference) on the in-line gage
transmitter is located on the neck of the transmitter via a protected gage
vent (See
Keep the vent path free from obstructions including but not limited to paint,
dust, and viscous fluids by mounting the transmitter so the process can drain
away.
Quick Start Guide
June 2020
4
Emerson.com/Rosemount
Содержание Rosemount 3051HT
Страница 25: ...Figure 3 1 Rosemount 3051HT Declaration of Conformity June 2020 Quick Start Guide Quick Start Guide 25 ...
Страница 26: ...Figure 3 2 Rosemount 3051HT Declaration of Conformity Quick Start Guide June 2020 26 Emerson com Rosemount ...
Страница 27: ...Figure 3 3 Rosemount 3051HT Declaration of Conformity June 2020 Quick Start Guide Quick Start Guide 27 ...
Страница 28: ...China RoHS Quick Start Guide June 2020 28 Emerson com Rosemount ...
Страница 29: ...June 2020 Quick Start Guide Quick Start Guide 29 ...
Страница 30: ...Quick Start Guide June 2020 30 Emerson com Rosemount ...
Страница 31: ...June 2020 Quick Start Guide Quick Start Guide 31 ...