4. Torque the bolts to the final torque value using the same crossing
pattern. See
for final torque value.
5. Verify that the flange bolts are protruding through the isolator plate
before applying pressure.
Table 2-1: Torque Values for the Flange and Flange Adapter Bolts
Bolt material
Head markings
Initial
torque
Final torque
CS
B7M
300 in-lb
650 in-lb
SST
316
316
316
SW
316
STM
316
R
B8M
150 in-lb
300 in-lb
2.1.5 In-line gage transmitter orientation
The low side pressure port (atmospheric reference) on the in-line gage
transmitter is located in the neck of the transmitter, behind the housing. The
vent path is 360° around the transmitter between the housing and sensor.
(See
)
Keep the vent path free of any obstruction, including but not limited to paint,
dust, and lubrication by mounting the transmitter so that the process can
drain away.
February 2019
Quick Start Guide
Quick Start Guide
9