Step 1: Mount the Transmitter

Step 2: Tagging

Step 3: Consider Housing Rotation

Step 4: Connect the Wiring and Power Up

Step 5: Verify Configuration

Step 6: Trim the Transmitter

Product Certifications

Start

End

Rosemount 3051 Pressure Transmitter with 
F

OUNDATION

 Fieldbus

Rosemount 3051CF Series Flowmeter Transmitter 
with F

OUNDATION

 Fieldbus

4774RevDA.fm  Page 1  Thursday, April 22, 2010  10:26 AM

Содержание Rosemount 3051

Страница 1: ...the Transmitter Step 2 Tagging Step 3 Consider Housing Rotation Step 4 Connect the Wiring and Power Up Step 5 Verify Configuration Step 6 Trim the Transmitter Product Certifications Start End Rosemount 3051 Pressure Transmitter with FOUNDATION Fieldbus Rosemount 3051CF Series Flowmeter Transmitter with FOUNDATION Fieldbus ...

Страница 2: ...figuration diagnostics maintenance service troubleshooting Explosion Proof Flame Proof or intrinsically safe I S installations Refer to the 3051 reference manual document number 00809 0100 4774 for more instruction This manual is also available electronically on www emersonprocess com rosemount WARNING Explosions could result in death or serious injury Installation of this transmitter in an explos...

Страница 3: ...ide of the line 2 Mount beside or below the taps 3 Mount the transmitter so that the drain vent valves are oriented upward Gas Flow Applications 1 Place taps in the top or side of the line 2 Mount beside or above the taps Steam Flow Applications 1 Place taps to the side of the line 2 Mount beside or below the taps 3 Fill impulse lines with water Flow ...

Страница 4: ...tallation Guide 00825 0100 4774 Rev DA April 2010 Rosemount 3051 4 STEP 1 CONTINUED Panel Mount 1 1 Panel bolts are customer supplied Pipe Mount Coplanar Flange Traditional Flange Rosemount 3051T Rosemount 3051H ...

Страница 5: ...nt representative for more information Use the following bolt installation procedure 1 Carbon steel bolts do not require lubrication and the stainless steel bolts are coated with a lubricant to ease installation However no additional lubricant should be applied when installing either type of bolt 2 Finger tighten the bolts 3 Torque the bolts to the initial torque value using a crossing pattern See...

Страница 6: ...lation to compensate for seating of the PTFE o ring Bolt Material Head Markings Initial Torque Final Torque Carbon Steel CS 300 in lbs 650 in lbs Stainless Steel SST 150 in lbs 300 in lbs Failure to install proper flange adapter O rings may cause process leaks which can result in death or serious injury The two flange adapters are distinguished by unique O ring grooves Only use the O ring that is ...

Страница 7: ...re 3 Inline Gage Low Side Pressure Port STEP 2 TAGGING Commissioning Paper Tag To identify which device is at a particular location use the removable tag provided with the transmitter Ensure that the physical device tag PD Tag field is properly entered in both places on the removable commissioning tag and tear off the bottom portion for each transmitter NOTE The device description loaded in the ho...

Страница 8: ...e housing rotation set screw Use of ordinary copper wire of sufficient size to ensure that the voltage across the transmitter power terminals does not drop below 9 vdc To power the transmitter connect the power leads to the terminals indicated on the terminal block label The power terminals are polarity insensitive which means the electrical polarity of the power leads does not matter when connect...

Страница 9: ...e cable shield should be grounded 1 Remove the Field Terminals housing cover 2 Connect the wiring pair and ground as indicated in Figure 4 The cable shield should a Be trimmed close and insulated from touching the transmitter housing b Continuously connect to the termination point c Be connected to a good earth ground at the power supply end Figure 4 Wiring 3 Replace the housing cover It is recomm...

Страница 10: ... point for shield wire to avoid creating a ground loop The ground point is typically at the power supply Signal Termination For every fieldbus segment a terminator should be installed at the beginning and at the end of each segment STEP 5 VERIFY CONFIGURATION Each Foundation fieldbus host or configuration tool has a different way of displaying and performing configurations Some use Device Descript...

Страница 11: ... mPa atm ftH20 68 F kg cm2 mmH20 4 C torr inH20 4 C Out_Scale Scale and Engineering Units Parameters Enter Data Channel 1 L_Type Direct XD_Scale See list of supported engineering units Note Only select the units that are supported by the device Out_Scale Set values outside operating range Parameters Enter Data Channel 1 L_Type Square Root XD_Scale 0 100 inH20 68 F Note Only select the units that a...

Страница 12: ...many Emerson Process Management Asia Pacific Private Limited Singapore Beijing Rosemount Far East Instrument Col Limited Beijing China Emerson Process Management Daman India European Directive Information The EC declaration of conformity can be found on page 17 The most recent revision can be found at www emersonprocess com Ordinary Location Certification for Factory Mutual As standard the transmi...

Страница 13: ...ups A B C and D hazardous locations Enclosure type 4X factory sealed For input parameters see control drawing 03031 1024 Single Seal European Certifications I1 ATEX Intrinsic Safety and Dust Certification No BAS 98ATEX1355X II 1 GD Ex ia IIC T4 Tamb 60 to 60 C Dust Rating Ex tD A20 T70 C Tamb 20 to 40 C IP66 1180 Special Conditions for Safe Use X When the optional transient protection terminal blo...

Страница 14: ... for Safe Use X This device contains a thin wall diaphragm Installation maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected The manufacturer s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime For more information on the dimensions of the flameproof joints contact the...

Страница 15: ...T6 Tamb 40 C Ex d IIC T5 Tamb 80 C DIP A21 T6 Tamb 40 C DIP A21 T5 Tamb 80 C IP65 Special Conditions for Safe Use X It is a condition of safe use for transmitter enclosures having cable entry thread other than metric conduit thread that the equipment be utilized with an appropriate certified thread adaptor N7 SAA Type n Non sparking Certification No AUS Ex 1249X Ex n IIC T4 Tamb 70 C IP66 Special ...

Страница 16: ...66 Combinations of Certifications Stainless steel certification tag is provided when optional approval is specified Once a device labeled with multiple approval types is installed it should not be reinstalled using any other approval types Permanently mark the approval label to distinguish it from unused approval types K5 E5 and I5 combination KB K5 and C6 combination KD K5 C6 I1 and E8 combinatio...

Страница 17: ...Quick Installation Guide 00825 0100 4774 Rev DA April 2010 Rosemount 3051 17 doc ...

Страница 18: ...Quick Installation Guide 00825 0100 4774 Rev DA April 2010 Rosemount 3051 18 ...

Страница 19: ...Quick Installation Guide 00825 0100 4774 Rev DA April 2010 Rosemount 3051 19 ...

Страница 20: ...Quick Installation Guide 00825 0100 4774 Rev DA April 2010 Rosemount 3051 20 ...

Отзывы: