condition exists. Check the device to determine the type of abnormal condition and
recommended actions to resolve it.
Plantweb alert priorities
Configure Plantweb
™
alert priorities in DeltaV
™
. Plantweb alerts can have any of 16
different condition prioritiesl, ranging from the lowest priority of 0 to the highest priority
of 15. This is done using the following parameters.
1. FAILED_PRI to specify the priority of FAILED_ALM
2. MAINT_PRI to specify the priority of MAINT_ALM
3. ADVISE_PRI to specify the priority of ADVISE_ALM
Plantweb alert priority is configured using DeltaV and is not part of the DD functionality.
2.7
Basic device setup
CAUTION
Set all transmitter hardware adjustments during commissioning to avoid exposing the
transmitter electronics to the plant environment after installation.
Note
The information contained within
is the same as in the Quick Start
Analog input (AI) function block
through
more detailed configuration information.
2.7.1
Configure
Each F
OUNDATION
Fieldbus host or configuration tool has a different way of displaying and
performing configurations. Some use DD methods for configuration and to display data
consistently across platforms. There is no requirement that a host or configuration tool
support these features. Use the following block examples to do basic configuration to the
transmitter. For more advanced configurations, reference
Analog input (AI) function block
in this manual.
Note
DeltaV
™
users should use DeltaV Explorer for the Resource and Transducer blocks and
control studio for the Function Blocks.
Configure the AI block
The screens used for each step are shown in
. In addition, step-by-step
instructions for each step of AI block configuration are provided in
.
Reference Manual
Configuration
00809-0100-4774
July 2020
Reference Manual
33
Содержание Rosemount 3051 CF Series
Страница 4: ...4 ...
Страница 56: ...Configuration Reference Manual July 2020 00809 0100 4774 56 Rosemount 3051 ...
Страница 92: ...Electrical installation Reference Manual July 2020 00809 0100 4774 92 Rosemount 3051 ...
Страница 102: ...Operation and maintenance Reference Manual July 2020 00809 0100 4774 102 Rosemount 3051 ...
Страница 118: ...Troubleshooting Reference Manual July 2020 00809 0100 4774 118 Rosemount 3051 ...
Страница 138: ...Reference data Reference Manual July 2020 00809 0100 4774 138 Rosemount 3051 ...
Страница 145: ...Reference Manual 00809 0100 4774 July 2020 Reference Manual 145 ...