3.3.4
2-Wire without Contact
Power supply:
•
19 to 230 Vac (50/60 Hz) +10%, 1.5 VA
•
19 to 230 Vdc +10%, 1 W
Load:
•
Minimum 10 mA
•
Maximum 0.5 A (fixed)
•
Load in example from PLC, relay, bulb, etc.
Fuse on power supply: maximum 4 A, slow or fast, HBC, 250 V
Note
See the Rosemount 2521
specifications.
Figure 3-6: 2-Wire: Power Supply and Load Connections
1 2
PE
Power supply
+
-
L
N
Load
Quick Start Guide
October 2020
22