2.3.1
System start-up
The standard start-up procedure of a Rosemount Tank Gauging system that includes devices such as the
Rosemount 2460 System Hub, Rosemount 2410 Tank Hub, Rosemount 5900S Radar Level Gauge, and
the Rosemount 2240S Multi-input Temperature Transmitter can be summarized as follows:
1. Install the devices on the appropriate locations.
2. Assign Modbus addresses
(1)
for the Rosemount 2410 Tank Hub, for level gauges such as the
Rosemount 5900S Radar Level Gauge, and for auxiliary tank devices (ATD) such as the Rosemount
2240S Multi-input Temperature Transmitter. The Modbus addresses will be stored in the built-in
databases of the Rosemount 2410 Tank Hub and the Rosemount 2460 System Hub.
3. Verify that the total current consumption of devices connected to the Tankbus does not exceed
250 mA
(2)
. In an Emerson Wireless system the maximum current is 200 mA.
4. Wire the devices.
Connect field devices to the Tankbus.
Note! Devices must be configured in the tank database
of the Rosemount 2410 Tank Hub in order
to be able to communicate on the Tankbus.
Connect the Rosemount 2410 Tank Hub to the Rosemount 2460 System Hub.
Connect the Rosemount 2460 System Hub to the control room PC with TankMaster software. The
2460 may be connected via a Rosemount 2180 Field Bus Modem, or directly via RS 232 or RS 485.
5. Install the TankMaster software in the control room PC.
6. Configure the devices by using the TankMaster WinSetup configuration tool as described in the
Rosemount Tank Gauging System Configuration Manual (Document no. 00809-0300-5100).
F
OUNDATION
™
fieldbus
To start up Rosemount Tank Gauging devices in a F
OUNDATION
fieldbus system:
1. Prepare the start-up by recording information that will be needed for configuration of various field
devices as described in the Rosemount Tank Gauging System Configuration manual. This may for
example include tank geometry, antenna type, number of temperature elements and other
configuration parameters.
2. Connect the field devices, such as the Rosemount 5900S Radar Level Gauge and the Rosemount
2240S Multi-input Temperature Transmitter, to the F
OUNDATION
fieldbus network.
3. Configure the field devices by using AMS Device Manager (or any other F
OUNDATION
fieldbus host
supporting DD4).
See the Reference Manual for the respective field device and the Rosemount Tank Gauging System
Configuration manual (Document No. 00809-0300-5100) for more information on how to configure
various Rosemount Tank Gauging devices. See section
“Technical documentation” on page 4
for a list of
available documentation.
1.
See the Rosemount Tank Gauging System Configuration Manual (Document no. 00809-0300-5100) for more information
2.
See the Rosemount 2410 Tank Hub Reference Manual (Document No. 00809-0100-2410) for more information
Содержание Rosemount 2230
Страница 1: ...Reference Manual 00809 0100 2230 Rev CA July 2017 Rosemount 2230 Graphical Field Display ...
Страница 2: ......
Страница 4: ...ii Reference Manual 00809 0100 2230 Rev CA Title Page July 2017 Title Page ...
Страница 16: ...6 Reference Manual 00809 0100 2230 Rev CA Introduction July 2017 Introduction ...
Страница 28: ...18 Reference Manual 00809 0100 2230 Rev CA Overview July 2017 Overview ...
Страница 44: ...34 Reference Manual 00809 0100 2230 Rev CA Installation July 2017 Installation ...
Страница 120: ...110 Reference Manual 00809 0100 2230 Rev CA Service and Troubleshooting July 2017 Service and Troubleshooting ...
Страница 132: ...122 Product Certifications Product Certifications July 2017 Reference Manual 00809 0100 2230 Rev CA ...
Страница 154: ...144 Reference Manual 00809 0100 2230 Rev CA Index July 2017 Index ...
Страница 155: ......