Section 2: Configure
April 2013
2.6.4
Damping
The damping command changes the response time of the transmitter; higher values can
smooth variations in output readings caused by rapid input changes. Determine the appropriate
damping setting based on the necessary response time, signal stability, and other requirements
of the loop dynamics within your system. The damping command utilizes floating point
configuration allowing the user to input any damping value within 0.0-60.0 seconds.
Damping with a Field Communicator
Enter desired Damping Value and select
APPLY
.
Damping with AMS Device Manager
Right click on the device and select
Configure
.
1.
Select
Manual Setup
.
2. Within the
Pressure Setup
box, enter desired damping value and click
Send
.
3. Carefully read the warning and click
Yes
if it is safe to apply the changes.
Damping with a Local Operator Interface
Reference
to enter damping values using an LOI.
Figure 2-11. Damping with LOI
From the
HOME
screen, enter the fast key sequence
Device Dashboard Fast Keys
2, 2, 1, 1, 5
EXTENDED MENU
CALIBRAT
DAMPING
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMLATE
HART REV
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXTENDED MENU
EXIT MENU
Содержание Rosemount 2051
Страница 2: ......
Страница 4: ......
Страница 102: ...92 Reference Manual 00809 0100 4107 Rev BA Section 6 Troubleshooting April 2013 Troubleshooting ...
Страница 213: ...203 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ...
Страница 214: ...204 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ...
Страница 227: ......