9
Reference Manual
00809-0100-4107, Rev BA
Section 2: Configure
April 2013
Table 2-1. Rosemount 2051 Device Revisions and files
2.4
Configuration basics
The Rosemount 2051 can be configured either before or after installation. Configuring the
transmitter on the bench using either a Field Communicator, AMS Device Manager, or Local
Operator Interface (LOI) ensures all transmitter components are in working order prior to
installation. Verify that the security switch is set in the unlock position (
) in order to proceed
with configuration. See
for switch location.
2.4.1
Configuring on the bench
To configure on the bench, required equipment includes a power supply, and a Field
Communicator, AMS Device Manager, or an LOI (option M4). Wire equipment as shown in
below. To ensure successful HART communication, a resistance of at least 250
s
must be present between the transmitter and the power supply, see
for details. Connect the Field Communicator leads to the terminals labeled
“COMM” on the terminal block or 1-5V configuration, wire as shown in
The Field communicator is connected to the terminals labeled VOUT/COMM.
Identify Device
Find Device Driver
Review
Instructions
Review
Functionality
Software
Release Date
NAMUR
Software
Revision
(1)
(1)
(1) NAMUR Software Revision is located on the hardware tag of the device.
HART
Software
Revision
(2)
(2) HART Software Revision can be read using a HART capable configuration tool.
HART
Universal
Revision
Device
Revision
(3)
(3) Device Driver file names use Device and DD Revision, e.g. 10_01. HART Protocol is designed to enable legacy device driver revisions to continue to
communicate with new HART devices. To access new functionality, the new Device Driver must be downloaded. It is recommended to download new
Device Driver files to ensure full functionality.
Manual
Document
Number
Changes to
Software
August 2012
1.0.0
01
7
10
00809-0100-4107
See footnote
(4)
for list of
changes.
(4) HART Revision 5 and 7 Selectable, Safety Certified, Local Operator Interface, Scaled Variable, Configurable Alarms, Expanded Engineering Units.
5
9
January 1998
N/A
178
5
3
00809-0100-4101
N/A
Set all transmitter hardware adjustments during commissioning to avoid exposing the
transmitter electronics to the plant environment after installation.
Содержание Rosemount 2051
Страница 2: ......
Страница 4: ......
Страница 102: ...92 Reference Manual 00809 0100 4107 Rev BA Section 6 Troubleshooting April 2013 Troubleshooting ...
Страница 213: ...203 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ...
Страница 214: ...204 Reference Manual 00809 0100 4107 Rev BA Appendix B Product Certifications April 2013 Product Certifications ...
Страница 227: ......