Service Mode
General Operation of RLDS - UI • 45
Recommended Refrigerant Gas Alarm Settings
Gas
Alarm Settings (PPM)
Leak
Spill
Evacuate
CO
2
/R-744
1500
2000
3000
FA188
100
300
500
FC72
100
300
500
H1301
100
300
500
H1211
100
300
500
H2402
100
300
500
H1234YF
100
300
500
HFP
100
300
500
N1230
100
300
500
NH
3
/R-717
50
150
300
R11
100
300
500
R12
100
300
500
R21
100
300
500
R22
100
300
500
R23
100
300
500
R32
100
300
500
R113
100
300
500
R114
100
300
500
R123
25
35
50
R124
100
300
500
R125
100
300
500
R134A
100
300
500
R227
100
300
500
R236FA
100
300
500
R245FA
100
300
500
R401A
100
300
500
R402A
100
300
500
R402B
100
300
500
R404A
100
300
500
R407A
100
300
500
R408A
100
300
500
R407C
100
300
500
R409A
100
300
500
R410A
100
300
500
R422A
100
300
500
Table 8-1
- Recommended Alarm Settings and Gas Enumeration