Type OSE

LABELLING

- 20 / + 60 °C   (bolting class 8-8)
- 30 / + 71 °C   (bolting A320L7)

CLAPET DE SECURITE

SLAM-SHUT VALVE

DN 25

505 2110 4670 7860 14850

50

80 100 150

PN 40 B

20 B1 50 J 50 B1 100 J 100 B2

25 B 16 B 20 J

Class

2   (bolting class 8-8)
-    (bolting A320L7)

Temperature TS

PN

Pumax

PT

PS

Cg

Other connections available (contact factory)

Security Class

BMS setting

Max only

Min only

All BMS 

types

DD MM YEAR

C60

(1)   BMS : Safety manometric box 
(2)  Differential strength (depending on BMS chosen)
(3)  Temperature depending on bolting material (see label)

Table 1.

 Technical Characteristics of the Type OSE Slam-Shut Valve

DN

25

50

80

100

150

Bypass

Cg

505

2110

4670

7860

14850

25

C1

35

35

35

32

33

35

Δ

P max 

(bar)

> 25

> 25

25

10

6

100

Relay travel 

(mm)

35

35

50

50

50

C50

Table 2.

 Flow Coef

fi

 cient, 

Δ

P max, Relay travel

Figure 2

. Label for Type OSE Slam-Shut Valve

OPERATING PRESSURE

Body, valve plug

PS

100 bar maxi

Associated BMS

(1)

 according to size

PSD

10 à 100 bar

Maximum Inlet Pressure

Pumax

100 bar

Type

DS

Differential strength

(2)

OPERATING TEMPERATURE

(3)

TS

- 20 / 60 °C
- 30 / 71 °C

SLAM-SHUT

Sizes available

DN

25, 50, 80, 100, 150

Norm

EN 14382

Operating class

A or B (see label, 

fi

 gure 2)

Accuracy

AG

2,5 – 5 (Piston)

Setpoint range 

Wdu-Wdo

0,010 à 100 bar

Response time

ta

< 1 s

Max Differential (valve closed) 

 

P max

100 bar

Max Differential (valve open)

P max

Voir tableau 2

Rearming

Manually after recti

fi

 cation of fault

Position indicator

On mechanism box

FLUID

Group 1 and 2 according to PED 97/23/CE, 1st and 2nd family gas according 
to EN 437, or other gases (compressed air, nitrogen). 

The gas must be noncorrosive, clean

 (

fi

 ltration on inlet side necessary) 

and dry

Содержание OSE Series

Страница 1: ...eter Tube interior Ø 8 10 mm Safety contact See D103683X012 manual INTRODUCTION Scope of Manual This manual provides installation start up maintenance and parts ordering information for the Type OSE Slam Shut Valve Information on other equipment used with this slam shut valve is found in separate manuals Product Description The OSE Slam Shut Valve protects transmission and distribution networks or...

Страница 2: ...ay travel mm 35 35 50 50 50 C50 Table 2 Flow Coefficient ΔP max Relay travel Figure 2 Label for Type OSE Slam Shut Valve OPERATING PRESSURE Body valve plug PS 100 bar maxi Associated BMS 1 according to size PSD 10 à 100 bar Maximum Inlet Pressure Pumax 100 bar Type DS Differential strength 2 OPERATING TEMPERATURE 3 TS 20 60 C 30 71 C SLAM SHUT Sizes available DN 25 50 80 100 150 Norm EN 14382 Oper...

Страница 3: ...0 62 334 220 124 17 50 20 150 254 76 346 220 152 26 50 300 267 83 346 220 165 29 100 600 287 83 346 220 165 32 80 20 150 298 95 380 220 190 43 50 300 318 105 380 220 210 48 100 600 337 105 380 220 210 55 100 20 150 353 114 420 220 229 74 50 300 368 127 420 220 154 82 100 600 394 137 420 220 273 98 150 20 150 451 140 424 220 357 150 50 300 473 159 424 220 357 166 100 600 508 178 424 220 357 202 C53...

Страница 4: ...ciple of Operation The slam shut valve is installed on the inlet side of the regulator on the horizontal pipeline The mechanism box should be situated on top see above schematic or on top for versions DN 25 50 80 Installation according to EN12186 is recommended Install according to direction of the fluid flow see arrow When assembling with adjacent elements care must be taken not to create pressur...

Страница 5: ...be checked periodically COMMISSIONING WARNING All interventions on the equipment should only be performed by qualified and trained personnel Preliminary verifications Start up positions Inlet and outlet valves Closed Verify absence of pressure between inlet and outlet valves Slam shut valve plug Closed Impulse isolation valve Closed Impulse atmospheric valve Open Setpoint Verification Using the at...

Страница 6: ...frequency Every 4 to 6 years or less depending on operating conditions In the case of BMS 162 or 071 it is highly recommended to check the condition of the diaphragm once yearly Verification Condition of O rings diaphragm and lubrication Replacement O rings diaphragm Tools Spanners 10 13 six sided wrench 6 Spanners According to DN size Francel spanner ref 197125 bypass and pin disassembly Valve pl...

Страница 7: ...k the valve plug or contact after sales If the valve closes Operating correctly Observe the evolution of the outlet pressure check tightness If the outlet pressure in the slam shut is decreases External leak Locate and seal the leak or contact after sales If the outlet pressure in the slam shut is constant Bleed off the outlet side of the regulator Observe the evolution of the outlet pressure chec...

Страница 8: ...972 548 3574 Asia Pacific Shanghai 201206 China Tel 86 21 2892 9000 Europe Bologna 40013 Italy Tel 39 051 419 0611 Middle East and Africa Dubai United Arab Emirates Tel 971 4811 8100 For further information visit www emersonprocess com regulators Natural Gas Technologies Emerson Process Management Regulator Technologies Inc USA Headquarters McKinney Texas 75070 USA Tel 1 800 558 5853 Outside U S 1...

Отзывы: