background image

Type OSE

Instruction Manual
D103687X012

November 2015

SLAM-SHUT VALVE

CONTENTS

Introduction  ........................................................................ 

1

Characteristics  ...................................................................  1

Labelling ............................................................................. 

2

Dimensions and Weights  ................................................... 

3

Operation  ........................................................................... 

4

Installation .......................................................................... 

4

Commissioning  .................................................................. 

5

Maintenance  ...................................................................... 

6

Spare Parts ........................................................................ 

7

Figure 1.

 Type OSE Slam-Shut Valve

The 

OSE 

is in conformity with the

Pressure Equipment Directif PED 97/23/CE

and is classi

fi

 ed under category IV.

CHARACTERISTICS

Material

Body Steel
Bonnet  

Steel

Ori

fi

 ce  

Stainless steel

Valve plug  

Stainless steel

O-rings  

Nitrile

Connections

Inlet/Outlet:  

ISO PN 100 B (ANSI 600 RF)

 

ISO PN 50 B (ANSI 300 RF)

 

ISO PN 20 B (ANSI 150 RF)

 

Other connections available

 (contact 

factory)

 

ISO PN 16 B, 25 B, 40 B

Impulse (IS):  

1/4’’ NPT threaded

Mechanism box vent (E):   1/4” NPT threaded
Impulse diameter:  

Tube interior Ø 8/10 mm

Safety contact:  

See D103683X012 manual

INTRODUCTION

Scope of Manual

This manual provides installation, start-up, maintenance, 
and parts ordering information for the Type OSE Slam-
Shut Valve. 

Information on other equipment used with this slam-shut 
valve is found in separate manuals.

Product Description

The 

OSE

 Slam-Shut Valve protects transmission and 

distribution networks or pipe lines supplying industries and 
commercial businesses.

It permits the gas 

fl

 ow to be cut off rapidly and totally in the 

case of under or over regulator pressure.

The OSE exists in DN 25 (1”) to DN 150 (6”). DN 200 (8”) 
and DN 250 (10”) are covered by the OSE LS.

The OSE consists of:

•  A body with a removable ori

fi

 ce, enclosed by a bonnet

•  A valve plug with integral bypass, tightshut by an O-ring

•  A release relay type OS2 including:

 

- A mechanism box (BM)

 

- A safety manometric box (BMS) to be connected on 

the outlet side of the pressure regulator.

Содержание OSE Series

Страница 1: ...eter Tube interior Ø 8 10 mm Safety contact See D103683X012 manual INTRODUCTION Scope of Manual This manual provides installation start up maintenance and parts ordering information for the Type OSE Slam Shut Valve Information on other equipment used with this slam shut valve is found in separate manuals Product Description The OSE Slam Shut Valve protects transmission and distribution networks or...

Страница 2: ...ay travel mm 35 35 50 50 50 C50 Table 2 Flow Coefficient ΔP max Relay travel Figure 2 Label for Type OSE Slam Shut Valve OPERATING PRESSURE Body valve plug PS 100 bar maxi Associated BMS 1 according to size PSD 10 à 100 bar Maximum Inlet Pressure Pumax 100 bar Type DS Differential strength 2 OPERATING TEMPERATURE 3 TS 20 60 C 30 71 C SLAM SHUT Sizes available DN 25 50 80 100 150 Norm EN 14382 Oper...

Страница 3: ...0 62 334 220 124 17 50 20 150 254 76 346 220 152 26 50 300 267 83 346 220 165 29 100 600 287 83 346 220 165 32 80 20 150 298 95 380 220 190 43 50 300 318 105 380 220 210 48 100 600 337 105 380 220 210 55 100 20 150 353 114 420 220 229 74 50 300 368 127 420 220 154 82 100 600 394 137 420 220 273 98 150 20 150 451 140 424 220 357 150 50 300 473 159 424 220 357 166 100 600 508 178 424 220 357 202 C53...

Страница 4: ...ciple of Operation The slam shut valve is installed on the inlet side of the regulator on the horizontal pipeline The mechanism box should be situated on top see above schematic or on top for versions DN 25 50 80 Installation according to EN12186 is recommended Install according to direction of the fluid flow see arrow When assembling with adjacent elements care must be taken not to create pressur...

Страница 5: ...be checked periodically COMMISSIONING WARNING All interventions on the equipment should only be performed by qualified and trained personnel Preliminary verifications Start up positions Inlet and outlet valves Closed Verify absence of pressure between inlet and outlet valves Slam shut valve plug Closed Impulse isolation valve Closed Impulse atmospheric valve Open Setpoint Verification Using the at...

Страница 6: ...frequency Every 4 to 6 years or less depending on operating conditions In the case of BMS 162 or 071 it is highly recommended to check the condition of the diaphragm once yearly Verification Condition of O rings diaphragm and lubrication Replacement O rings diaphragm Tools Spanners 10 13 six sided wrench 6 Spanners According to DN size Francel spanner ref 197125 bypass and pin disassembly Valve pl...

Страница 7: ...k the valve plug or contact after sales If the valve closes Operating correctly Observe the evolution of the outlet pressure check tightness If the outlet pressure in the slam shut is decreases External leak Locate and seal the leak or contact after sales If the outlet pressure in the slam shut is constant Bleed off the outlet side of the regulator Observe the evolution of the outlet pressure chec...

Страница 8: ...972 548 3574 Asia Pacific Shanghai 201206 China Tel 86 21 2892 9000 Europe Bologna 40013 Italy Tel 39 051 419 0611 Middle East and Africa Dubai United Arab Emirates Tel 971 4811 8100 For further information visit www emersonprocess com regulators Natural Gas Technologies Emerson Process Management Regulator Technologies Inc USA Headquarters McKinney Texas 75070 USA Tel 1 800 558 5853 Outside U S 1...

Отзывы: