NetSure 211 C23 Embedded Power 

Supply System

 

User Manual

 

 

Version              V1.0 

Revision date    September 15, 2009 

BOM                    31012177 

 

 

Emerson Network Power provides customers with 

technical support. Users may contact the nearest 

Emerson local sales office or service center. 

 

 

Copyright © 2009 by Emerson Network Power 

Co., Ltd. 

All rights reserved. The contents in this document 

are subject to change without notice. 

 

Emerson Network Power Co., Ltd. 

Address: No.1 Kefa Rd., Science & Industry Park, 

Nanshan District 518057, Shenzhen China 

Homepage: www.emersonnetworkpower.com.cn 

E-mail: [email protected] 

 

Содержание NetSure 211 C23

Страница 1: ...y contact the nearest Emerson local sales office or service center Copyright 2009 by Emerson Network Power Co Ltd All rights reserved The contents in this document are subject to change without notice Emerson Network Power Co Ltd Address No 1 Kefa Rd Science Industry Park Nanshan District 518057 Shenzhen China Homepage www emersonnetworkpower com cn E mail support emersonnetwork com cn ...

Страница 2: ... system The installation personnel must be licensed to operate high voltage and AC power In operation the installation personnel are not allowed to wear conductive objects such as watches bracelets bangles and rings When you spot the cabinet with water or moisture turn off the power immediately In moist environment precautions must be taken to keep moisture out of the power supply system Prohibit ...

Страница 3: ...hat when the tool in operation slips the movement of the human body and tool is reduced to a minimum BLVD The power supply system has battery low voltage disconnection BLVD function BLVD means when battery voltage drops down to 43 2V the power supply system cuts the load off to prevent over discharge BLVD is enabled before delivery which means that if power outage lasts for a long time or the powe...

Страница 4: ...uses to meet the safety requirement II Sharp object Warning When moving equipment by hand wear protective gloves to avoid injury by sharp object III Power cable Warning Notice Note Please verify the cable labels before connection IV Signal cables Warning Notice Note The signal cables should be routed at least 150mm away from power cables ...

Страница 5: ... 4 Electrical Installation 5 2 4 1 Connecting Power Cables 5 2 4 2 Connecting Signal Cables 6 Chapter 3 Installation Testing 7 3 1 Installation Check And Startup 7 3 2 Basic Settings 8 3 3 Alarm Check And System Operation Status Check 8 3 4 Final Steps 9 Chapter 4 Alarm Handling 10 4 1 Handling Alarms 10 4 2 Handling Rectifier Fault 11 Appendix 1 Technical Data 14 Appendix 2 Wiring Diagram 16 Appe...

Страница 6: ......

Страница 7: ...erminals Monitoring module Rectifier Figure 1 2 Appearance of the system The configuration of the system is listed in Table 1 1 Table 1 1 Configuration of the system Component Configuration Rectifier Model R48 1000 Standard configuration 2 pieces Monitoring module Model M522B M523B or M221B Standard configuration 1 piece AC power distribution AC input mode L N PE 220V DC power distribution 10 load...

Страница 8: ...to replace a rectifier The rectifier has two over voltage protection methods hardware protection and software protection The latter one also has two optional modes lock out at the first over voltage and lock out at the second over voltage The monitoring module has perfect battery management The management functions include battery low voltage disconnection BLVD temperature compensation auto voltag...

Страница 9: ...n The equipment should be unpacked and inspected after it arrives at the installation site The inspection shall be done by representatives of both the user and Emerson Network Power Co Ltd To inspect the equipment you should open the packing case take out the packing list and check against the packing list that the equipment is correct and complete Make sure that the equipment is delivered intact ...

Страница 10: ...e and not less than 2 5mm2 The RS232 cable is shown in Figure 2 1 DB9 X1 RJ45 X2 A amplified view A Figure 2 1 RS232 cable The definition of the RS232 cable connector is shown in Table 2 4 Users should make RS232 cable according to the description in Table 2 4 Table 2 4 Definition of the RS232 cable connector DB9 RJ45 X1 2 X2 3 X1 3 X2 6 X1 4 X2 7 X1 5 X2 4 X2 5 X1 6 X2 2 X1 7 X2 8 X1 8 X2 1 2 3 M...

Страница 11: ...ttery MCBs at the battery side are switched off If there are no battery MCBs at the battery side you should disconnect any one of the connectors between battery cells to avoid live state of the system after installation 4 Be careful not to reversely connect the battery Otherwise both the battery and the system will be damaged The positions of connection terminals are shown in Figure 2 3 DI DO temp...

Страница 12: ...nal is shown in Figure 2 3 and the screen print is shown in Figure 2 4 NO COM NO COM PS Ground T1 T2 DO2 DO1 DI2 DI1 Temp sensor Figure 2 4 DI DO temperature probe connection terminal Connection method Peel one end of the signal cable and insert it into the DI DO temperature probe connection terminal Fasten the connection by tightening the screw on the terminal Warning Notice Note The output dry c...

Страница 13: ...sensor if any has been installed correctly Startup preparations Check item OK Comments Make sure that all the MCB are switched off and all the fuses are removed Measure the AC input voltage Make sure the input voltage is within the allowable range Umin ___V Check that the battery string circuit is not closed Connect the disconnected batteries to the battery string circuit Measure with a voltmeter ...

Страница 14: ... 4V For batteries that do not need BC set the BC voltage to FC voltage plus 0 1V Measure the battery voltage with a multimeter and record it Enter main menu Maintenance password 1 RectTrim submenu Set the output voltage of the rectifier to the value of the battery voltage Insert the battery fuse Set the output voltage of the rectifier to 53 5V Enter the Batt Selection submenu Set the Mode paramete...

Страница 15: ...r should be consistent with the actual number Check the voltage current current limiting point of rectifiers through the monitoring module They should agree with the actual parameters For the system configured with temperature sensor the monitoring module should display the battery ambient temperature Hold the probe of the temperature sensor and watch the monitoring module which should display the...

Страница 16: ...ver voltage point is too low If yes reset the value A mild over voltage does not affect the system operation However the rectifier will stop operation when the mains voltage is more than 305V Therefore if the power supply voltage is often high consult with the power grid maintenance personnel to improve it 3 AC Voltage Low Check if the AC Under voltage point is too high If yes reset the value When...

Страница 17: ...re is a battery internal fault If yes replace the battery 2 Check if the battery room temperature is too high If yes cool down the battery room 4 2 Handling Rectifier Fault Handling indicator fault The symptoms of usual rectifier faults include green indicator run indicator off yellow indicator protection indicator on yellow indicator blink red indicator fault indicator on and red indicator blink ...

Страница 18: ...ce 3 Check whether the rectifier communication is normal If not check whether the communication cable is in normal connection If the communication is normal while the protection indicator is on replace the rectifier Red indicator blinks Rect Fan Fails Fan fault Replace the fan Replacing rectifier fan If the rectifier fan is faulty it should be replaced Refer to Figure 4 2 for the replacing procedu...

Страница 19: ...1 The monitoring module recognizes the new rectifier 2 The new rectifier shares current with other rectifiers 3 When this new rectifier is pulled out there is a corresponding alarm and the monitoring module displays the alarm If the new rectifier passes all the above tests the replacement is a success 6 Push the handle back into the front panel to lock the rectifier 7 Fix the fixing screw of the h...

Страница 20: ...le AC input under voltage alarm recovery point 15Vac higher than the AC input under voltage alarm point AC input over voltage protection point Default 305Vac 5Vac AC input over voltage protection recovery point 10Vac lower than the AC input over voltage protection point AC input under voltage protection point Default 80Vac 5Vac AC input under voltage protection recovery point 15Vac higher than the...

Страница 21: ... within a set time default 5min Configurable through monitoring module the rectifier will shut down and hold that state Manual resetting is required to restore the operation Manual resetting Resetting can be done manually through the monitoring module or by removing the rectifier from system Temperature derating 20 C 45 C 1000W 45 C 75 C linear derating 75 C 0W EMC CE Class A EN55022 RE Immunity t...

Страница 22: ...2 2 1 X2 1 1 X1 1 1 X1 2 1 X1 6 6 PE 6 L 6 N 1 J2 1 J1 2 4 2 2 6 AC Connector 7 BAT INPUT N PE L Front pannel connection of the DU area BAT BAT 1 J3 1 J4 Back View 3 PE 3 N 3 L J2 J3 J7 3 J218 7 BAT 2 35 LOAD OUTPUTS 2 47 2 49 1 X1 4 1 Busbar 1 2 BLVD Shunt 4 44 4 32 2 1 LOAD9 LOAD10 W02 LOAD8 FUSE10 LOAD7 FUSE9 LOAD6 FUSE8 LOAD5 FUSE7 LOAD4 FUSE6 LOAD3 FUSE5 LOAD2 FUSE4 LOAD1 FUSE3 FUSE2 FUSE1 BA...

Страница 23: ... Limit CycBC Cyclic Boost Charging Con Alarm Voice Control Alarm Voice Hist Alarm Historical alarm HVSD High Voltage Shutdown InitParam Initialize Parameters InitPWD Initialize Password LLVD Load Low Voltage Disconnection LVD Low Voltage Disconnection MCB Miniature Circuit Breaker Ph A Phase A PWD Password Rect Rectifier Shunt coeff Shunt Coefficient SPD Surge Protection Device SW Version Software...