MODBUS RTU COMMUNICATIONS
These MODBUS RTU Communication instructions are specific to the Modbus communications setup for the
CM-1 Monitoring System. Modbus communications are only provided on recent production Scanner Board
GC0698.
Wiring Instruction
From modbus master
Modbus connection wire A connects to Scanner Board GC0698 - TB5 – 7
Modbus connection wire B connects to Scanner Board GC0698 - TB5 – 9
Address settings:
•
S1 =
Ones (0-9)
•
S2 =
Tens (10-90)
Communications settings:
•
Baud Rate =
4800
•
Data Bits =
8
•
Stop Bits =
1
•
Parity =
None
CM-1 Register Addresses/Descriptions
Write (06) address:
40000
Data = 1, acknowledges all alarms, Data = 2, resets board/all alarms
Read (03) addresses:
40000 - 40023 Channel Flag Table*
40256 - 40264
CM-1 Board ID String (ASCII)
40512
Option Jumpers 1-8
40768
Option Jumpers 9-16
*Channel Flag Bit Significance:
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
b15 – b10
Not Used
b9
Series Mode
b8
Parallel Mode
b7
Channel ON
b6
Channel in Alarm
b5
Alarm Pending
b4
Alarm Acknowledged
b3
Not Used
b2
Continuity Out of Tolerance
b1
Current Out of Tolerance
b0
Voltage Out of Tolerance
S2 S1
Содержание Nelson CM-1
Страница 1: ...CM 1 CIRCUIT MONITORING SYSTEM ...
Страница 2: ......
Страница 12: ...www nelsonheaters com GA 2129 Rev 11 Sheet 12 of 22 Jul 2018 Figure 12 ...
Страница 19: ...www nelsonheaters com GA 2129 Rev 11 Sheet 19 of 22 Jul 2018 FIELD WIRING DIAGRAM ...
Страница 20: ...www nelsonheaters com GA 2129 Rev 11 Sheet 20 of 22 Jul 2018 ...
Страница 21: ...www nelsonheaters com GA 2129 Rev 11 Sheet 21 of 22 Jul 2018 ...
Страница 22: ...www nelsonheaters com GA 2129 Rev 11 Sheet 22 of 22 Jul 2018 NOTES ...
Страница 23: ......