The Plug-In Output Board
Mounting and Powering • 3
2.2. The Plug-In Output Board
The MultiFlex RTU has an output sub-board that
plugs to the top of the base board. Typically,
these boards are shipped with the output board
pre-installed on the board using stand-offs, so no
additional hardware setup should be necessary.
The additional board makes the MultiFlex RTU
boards considerably taller than the MultiFlex 16
and other Emerson I/O boards. If you will be
mounting these boards in an enclosure, the board
will need at least 2.5" of clearance between the
base board and the panel door.
2.3. Powering the MultiFlex
RTU Board
All models of MultiFlex require a 24VAC Class
2 input power source. The MultiFlex RTU
requires the power source to be
non-center-tapped.
Emerson supplies a wide variety of 24VAC
transformers with varying sizes and either with
shows the
transformer sizes and whether they are center-
tapped or non-center-tapped.
Figure 2-3
- Exploded View — MultiFlex RTU
Xformer P/N
VA Rating
Primary Voltage
Center Tap?
640-0041
50 VA
110 VAC
No
640-0042
50 VA
220 VAC
No
640-0056
56 VA
Multi-tap (120/208/240 VAC)
Yes
640-0050
75 VA
110 VAC
No
640-0045
75 VA
220 VAC
No
640-0080
80 VA
Multi-tap (120/208/240 VAC)
Yes
Table 2-1
- Transformers Compatible with MultiFlex