background image

 

Page 2

1.0  Safety Information 

 
 

Warning :

 

If this equipment is used in a manner not specified by the manufacturer, the protection provided may be 
impaired.  All installation and commissioning of this equipment must be carried out by electrically 
competent persons.

 

 
 
1.1  Protection of permanently installed equipment : 

 
This equipment is intended to be permanently installed equipment.   Ensure wiring is suitable for the load current and the 
insulation is suitable for the voltage, temperature and environment of the installation. 
 
A supply disconnection device must be included in the installation, fitted as close as practical to and not be obstructed by the 
equipment.  It must be double pole and marked as the disconnection device.  Each relay circuit must be protected by a fuse not 
exceeding the maximum rated current for the relay as specified in the manual. 
 
On wall mount unit disconnect supply before removing control unit from base.  Control units must be correctly assembled to 
achieve stated IP ratings. 
 

1.2  Explanation of symbols : 

 
The IEC symbols used on the equipment are as follows : 
 

Refer to Manual. 

 
 
 

 
The Protective earth terminal must be connected to an external Protective earthing system. 

 

 
2.0  Application 

The Electrosensor system is used for the detection of liquids or liquids with suspended / settled solids. 
 

2.1  Technical Description 

The control unit type MES*L is intended for mains powered operation in a control room non-hazardous area.  The Mobrey 
Electrosensor liquid level sensor in the hazardous area is connected directly to this control unit over a twisted pair cable or 
similar.  The connection provides nominal 12V dc power to the electrosensor head or adjacent amplifier, and the MES*L control 
unit monitors the current drawn to identify the sensor state.  This is either 8 or 16mA.  See instruction manual IP264 for further 
information. The output relay of the MES*L is set according to this sensor current and the setting of switch 1 (See Fig. 3). 
 
Fault monitoring is achieved by checking the current drawn is within the band 4mA to 20mA.  If a fault state exists 
(current outside of band) then the fault relay de-energises. 
 
For instructions specific to units used in hazardous area installations refer to leaflet IP242/SI 
 

Beware 

A thermal safety cut out in the transformer will fuse if 115V units are powered with 230V mains supplies. 
 

3.0  Installation 

 
The control units should be installed in an area suitable for their specifications.  They are designed to be used indoors, but could 
be installed outside using a suitable weatherproof enclosure.  The front panel should be accessible to the operator. 
 
The standard control unit MES*L is installed by undoing the two screws on the top and bottom of the unit, and 
removing from the base.  The base can now be mounted as required, making sure that the connection terminals are 
on the left-hand side of the base. 
 
The control unit has two relays, one for normal / alarm signaling and one for fault.  They are both single pole change 
over (SPCO).  The internal switches (see Switch Setting Adjustment section) select the alarm relay normal condition 
(energised or de-energised).  If an alarm condition occurs the relay will change state.  The fault relay is normally 
energised and will release if an under or over current condition occurs.  A 5 amp HBC fuse should be included in each 
relay circuit. 
 

 
3.1  Wiring 

The system is designed to be noise immune; however, it is good practice to separate the instrumentation cables from 
power cables.  Figure 1 shows the terminal arrangements.  If a single sensor is used its cable cores are connected to 
the 1(-) and 2 (+) terminals on the control unit.  If two sensors are used the high level one is connected to terminals 1 
and 2 as above and the low level sensor is connected to terminals 3  (+) and 4 (-).  The screen is earthed at the  

 

Содержание Mobrey Electrosensor

Страница 1: ... CONTENTS 1 0 Safety information 2 1 1 Protection 2 1 2 Explanation of symbols 2 2 0 Application 2 2 1 Technical description 2 3 0 Installation 2 3 1 Wiring 2 3 2 Terminal arrangements 3 3 3 Printed circuit board 3 3 4 Switch setting adjustment 4 4 0 Technical specifications 4 5 0 Model identification 5 6 0 Maintenance Inspection 5 ...

Страница 2: ...See instruction manual IP264 for further information The output relay of the MES L is set according to this sensor current and the setting of switch 1 See Fig 3 Fault monitoring is achieved by checking the current drawn is within the band 4mA to 20mA If a fault state exists current outside of band then the fault relay de energises For instructions specific to units used in hazardous area installat...

Страница 3: ...ectrical noise 3 2 Terminal arrangements Figure 1 MES L Terminals Connections Notes Relay terminals are shown in the de energised state Terminals 2 3 are linked on the MES L pcb and can use one field cable core if required When two sensors are used with one control unit for a pump control application the sensor on terminals 1 2 must be the top sensor and the lower liquid level sensor must be attac...

Страница 4: ...Technical Specifications Main relay output 5 amp SPCO resistive 250V a c Fault relay 5 amp SPCO resistive 250V a c Power supply 110 120v a c 10 220 240v a c 10 50 60 Hz Temperature range 20 C to 65 C Housing IP20 enclosure designed for wall mounting with 2 screws Optional DIN rail adaptor available Dimensions mm H 150 x W 75 x D 112 Mounting holes 2 x 3mm Ø on C L 100mm apart Sensor power for 1 or...

Страница 5: ... Code Voltage requirements 1 220 240V ac 50 60 Hz 2 110 120V ac 50 60 Hz Code Output relay S SPCO MES 3 L 1 S 6 0 Maintenance Inspection This is limited to periodic inspection by a qualified person to ensure that the installation including wiring and equipment housing is safe Clean only with a damp cloth ensuring that no moisture enters control unit Check unit for damage and if damaged do not use ...

Страница 6: ...Page 6 ...

Страница 7: ...Page 7 ...

Страница 8: ...3589 mobrey sales EmersonProcess com www mobrey com Mobrey SA NV Belgium tel 02 465 3879 Mobrey GmbH Deutschland tel 0211 99 808 0 Mobrey SA France tel 01 30 17 40 80 Mobrey sp z o o Polska tel 022 871 7865 Mobrey AB Sverige tel 08 725 01 00 2005 Mobrey The right is reserved to amend details given in this publication without notice ABCDEF ...

Отзывы: