46
Model IFT9701 Transmitter Instruction Manual
Configuration with ProLink II Software
continued
7.2
Configuration parameters
Use the Configuration window to perform the following tasks:
•
Assigning a HART tag to the flowmeter
•
Changing process variable measurement:
-
Changing measurement units for the mass flow or volume flow rate
-
Changing the flow cutoff value
-
Changing the internal damping value
-
Changing the flow direction parameter
•
Setting range values for the milliamp output
•
Scaling the pulse output
7.2.1
HART tag
The HART tag consists of up to eight characters that identify the flowmeter when it communicates
with other devices in a HART multidrop network.
To assign a HART tag to a flowmeter:
1. From the ProLink menu, click on Configuration.
2. In the Configuration window, click on the Device tab.
3. When the Device panel appears (as depicted in Figure 7-1), enter the desired tag of up to eight
characters, then click on OK. The tag can include spaces and periods.
Figure 7-1
Configuration window – Device panel