Liebert’s transfer control does

more than balance the flux.

Due to our unique approach to the

optimized transfer algorithm, transfer

time should not be the only performance

measure for this new optimized switch.

Liebert’s method, whenever possible,

also seeks to minimize voltage

disturbances while maintaining

transformer flux balance. It takes both

voltage disturbance and volt-second

balance into consideration.

Liebert has a unique flux balance

algorithm that doesn’t just “sit and

wait” for the balance point to occur.

Rather, we will “pulse fire” the SCRs

as soon as possible in order to

minimize the load discontinuity and

hence the voltage disruption.

So how safe is this new

optimized Liebert STS2 for your

critical loads?

The optimized Liebert STS2 safely meets

both the CBEMA standard (prior to 1996)

and the latest ITIC standard (1996) for

critical loads. Liebert’s optimized 

STS2 eliminates the risk of transformer

saturation problems during automatic

transfers, while its algorithm control

ensures minimum voltage disturbance

during transfers while still balancing 

the flux.

Figure 2

Optimized STS transfer 

The patented Liebert static switch optimized transfer control algorithm

eliminates the downstream transformer inrush saturation.

The Liebert algorithm is designed to optimize transfer timing such that the volt-seconds applied to the

downstream transformer primary is balanced, thus minimizing peak saturation current. This balance is

achieved by directly computing the volt-second applied to the transformer during transfer events and

determining the optimum time to turn on the alternate source SCRs in order to balance the volt-

second within specified tolerance. 

This results in a volt-second balancing algorithm that is independent of voltage wave shape,

voltage failure decay rate, etc., making it superior to other algorithms based on voltage

phase angle difference only.

 

Содержание Liebert STS2

Страница 1: ...AC Power For Business Critical Continuity Liebert STS2 Static Transfer Switch2 The Cornerstone of High Availability Power Systems ...

Страница 2: ...low maintenance service or full replacement without disrupting the critical load Flexibility Internal CANBUS protocol high bandwidth communication between system components via twisted pair cables Options can be added as simple network nodes Dual lug installation bus with pem nuts for single hand installation and hot torque service Low Total Cost Of Ownership Conservative design margins and excell...

Страница 3: ...t without shutting down the connected load For units up to 600 amps the entire power and control module can be removed as an assembly A separate compartment for option modules provides safe and convenient field access Source 1 Source 2 System Output CB1 CB3 CB4 CB2 CB5 K1 K2 K2 K3 K1 K3 True Internal Redundancy The Liebert STS2 has triple redundant logic Each DSP controller is capable of working i...

Страница 4: ...switching is lower cost These savings are the result of only one power distribution unit a lower current due to 480V vs 208V and lower installation and wiring cost thanks to use of smaller three wire cable The one drawback of this configuration is the creation of transformer inrush saturation current each time switching occurs The downstream transformer can cause large peak saturation current duri...

Страница 5: ...r critical loads Liebert s optimized STS2 eliminates the risk of transformer saturation problems during automatic transfers while its algorithm control ensures minimum voltage disturbance during transfers while still balancing the flux Figure 2 Optimized STS transfer The patented Liebert static switch optimized transfer control algorithm eliminates the downstream transformer inrush saturation The ...

Страница 6: ...utput Breaker An output plug in non automatic circuit breaker provides redundancy in the output power path The breaker is connected in parallel with the output plug in non automatic circuit breaker Input Junction Boxes and Cable Up to 600A The input junction box option is available to simplify input connections to the STS2 Two input junction boxes and the associated flexible 10 foot long input cab...

Страница 7: ...hat equipment s operating status at any given time For customers who need to have these vital protection systems continuously monitored but don t want to do it themselves Emerson Network Power Service offers Remote Monitoring Service This seamless rapid response system is designed to maximize the capabilities of your Liebert equipment by maximizing the effectiveness of its monitoring capabilities ...

Страница 8: ...omissions 2006 Liebert Corporation All rights reserved throughout the world Specifications subject to change without notice All names referred to are trademarks or registered trademarks of their respective owners Liebert and the Liebert logo are registered trademarks of the Liebert Corporation SL 20600 R03 08 Printed in USA Ensuring The High Availability Of Mission Critical Data And Applications H...

Отзывы: