REV. 5
7/6/2007
Liebert Monitoring Group –Development
23
Input Current L2
30204
1 1
A
Input Voltage L3
30253
1
1
V
Input Current L3
30254
1 1
A
Liebert UPS Series 600
Supported Modbus Points
Data Point
Status
Coil
# of
Reg.
Scale
Notes / Units
Battery Charger On
10044
1
1
Battery Charge
Compensation
10046
1
1
Inverter Ready
10047
1
1
Auto Retransfer
Primed
10049
1
1
Load On Inverter
10073
1
1
Load On Bypass
10074
1
1
Buck On
10076
1
1
Battery data Buffer Full
10084
1
1
Shutdown Reason –
Hardware
10096
1
1
Load On Battery
10128
1
1
Manual Reset Transfer
10130
1
1
Load On Bypass
Permanent
10133
1
1
Load On Bypass-UPS
fault
10134
1
1
Battery Switch Open
10136
1
1
Input Switch Open
10137
1
1
Output Switch open
10138
1
1
Emergency Load
Transfer to Inverter
10145
1
1
Transfer inhibited –
Asynchronous
Sources
10146
1
1
Transfer inhibited –
over predefined limit
10147
1
1
SBS SCR Open
10149
1
1
SBS SCR Short
10150
1
1
Low Battery -
Shutdown Imminent
10152
1
1
Output Overload
10154
1
1
Over Temperature
Warning
10171
1
1
Battery Over
Temperature CB Trip
10172
1
1
Input Power Supply
Fail
10186
1
1
Input Under Voltage
10188
1
1
Input Brown Out
10189
1
1