UPS Electrical Installation
10
2.4
Control Cable and Communication
Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery
system (external battery circuit breaker), communicate with a personal computer or provide alarm
signaling to external devices, or for Remote Emergency Power Off (REPO). The External Interface
Board, arranged for this purpose, is next to the option box in the Rectifier section (refer to
4.0 -
Installation Drawings
).
Figure 5
External Interface Board connections layout
2.4.1 Dry Contacts
NOTE
If connection to more than one module is required, use a separate, isolated contact for each
module.
Table 1
UPS input dry contacts
Item
Terminal
Block
Pin
Connects to
(Description of External Item)
Wire Size/
Max Length
Remote EPO
Input Form C
TB0824
1
REPO Switch, normally open contact
14AWG/
500ft.
(150m)
2
REPO Switch, common contact
3
REPO Switch, normally closed contact, set jumper
J5: 1-2 to enable, 2-3 to disable
On Generator
Input Form C
TB0816
1
On Generator switch, closed = On Generator
2
On Generator switch, common
3
On Generator switch,
closed = Not On Generator
P66C
P99C
TB0823
EPO
STATUS
TB0829
EXTERNA L
CAN
TB1154B
TB1154A
TB0825
TB0824
TB0826
TB0820
TB0818
TB0817
TB0819
TB0816
TB0830
TB035
TB0821
P0801
TB0811
TB0810
TB0813
TB0812
TB0815
P0832
P0831
P0808
OPT
PS
INT BATT
CAN
EXT BATT
CAN
REPO
J4
REPO
FORM C
LBS VO LTAGE
EXTERNA L
CAN
MOB
MIB
RIB
MBB
BIB
KEY
STATUS
INV
CNTRLN
RECT
CNTL
BYP CNTL
ON GEN
ACT FILT
STATUS
BATT GND
FLT
ACT FILT
CNTL
MAINT BYP
ENABLE
AUX SPARE
TEMP
J5
BATT MTR
OP
TB1156