UPS Alarm and Status Messages
79
Liebert
®
NXL
™
A
PPENDIX
A - UPS A
LARM
AND
S
TATUS
M
ESSAGES
shows alarm and status messages as they appear in the Liebert NXL’s touchscreen and in
the history log, along with a description and recommended actions, if any.
If the recommended action fails to correct the condition, contact your factory-authorized service pro-
vider.
The “Service Telephone Number” can be found by pressing “CONFIG,” “Ratings,” “More>>” on the
menu bar.
NOTE
In Event log, take the number for the “Data” Column. Convert that number from Decimal to
Hex. Each digit will explain the reason for the Inhibit signals.
Example:
Data = 512d =0200h->“Removing Module will cause Overload or Drop the Load”
Table 10
Liebert NXL alarm and status messages
Event Message
Event Definition
Recommended Action
Auto Restart Fail
An Automatic Restart was enabled, but has
failed to complete.
With Automatic Restart enabled, the unit
automatically restarts after an End of Discharge
(EOD) event. This alarm means that one of the
auto restart requirements was true, but failed
before the restart sequence completed.
For example, one conditional requirement for
Automatic Restart to occur is that the Rectifier
Input Voltage must be within acceptable limits. If,
during the restart sequence, the input voltage
drops out of tolerance, the Automatic Restart will
fail.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
Press “SILENCE” to silence the audible alarm.
Check the active events to determine the status of
the UPS.
If “Auto Restart Fail” is the only alarm present,
attempt a manual start of the unit by pressing
“Startup,” “Manual Start,” then following the
prompts to attempt to place the unit back online.
If the manual start fails, or if there are other alarms
present that won’t clear, contact your factory-
authorized service provider.
Auto Rexfer
Failed
The condition that caused the system to
automatically disconnect the inverter from the
critical bus has failed to clear within a specified
time delay.
An example of a recoverable condition (one
which the controls may attempt to recover from
automatically) is an overload that exceeded the
overload capability.
Press “SILENCE” to silence the audible alarm.
Press “RESET” to attempt to clear active events.
This does not clear the “Auto Retransfer Failed”
alarm.
If all other alarm conditions are clear, for a single
module system attempt a manual transfer to
Inverter by pressing “Transfer,” “UPS.” For a multi-
module system attempt to manually reconnect this
inverter by pressing “Transfer,” “Connect This
Inverter.”
If successful, press “RESET” to clear this alarm
from the Active Event Window. If the UPS fails
connect the inverter to the critical bus and the
active messages do not explain the reason,
contact your factory-authorized service provider.
Bat Mon 1 Critical
Battery Monitor 1 is reporting a critical alarm.
Check the Battery Monitor Module for more details
on this condition.
Contact your factory-authorized service
representative for service.
Bat Mon 1 Maint
Battery Monitor 1 has an active Maintenance
Alarm.
Check the Battery Monitor Module for more details
on this condition.
Contact your factory-authorized service
representative for service.
Batt CB“#” Open
Battery Circuit Breaker “#” is open.
This status message is self-clearing. When the
condition is no longer present, the message and
any control activity tied to the status event
reverts to normal.
Press “SILENCE” to silence the audible alarm.
Check the status of Battery Circuit Breaker 1. If it is
open, the alarm is normal.
If Battery Circuit Breaker 1 is closed, contact your
factory-authorized service provider.
Содержание Liebert NXL 250 kVA
Страница 8: ...vi ...
Страница 51: ...Operation 43 Liebert NXL Figure 42 1 N UPS Transfer to Inverter menu commands ...
Страница 57: ...Operation 49 Liebert NXL Figure 45 1 N UPS shutdown menu commands ...
Страница 86: ...Specifications Liebert NXL 78 ...
Страница 110: ...UPS Alarm and Status Messages Liebert NXL 102 NOTES ...