Operation
47
Liebert
®
NXL
™
2.15.14 Shutdown—N+1 UPS System
Perform a Module Shutdown Procedure when you want to disconnect power from a UPS module. For
System shutdown, see the SCC operation and maintenance manual, SL-25514, available at the
Liebert Web site:
before performing any maintenance on a Liebert NXL UPS.
These warnings and cautions must be observed during any work on the UPS.
Use the module Monitor/Mimic Display to determine the operating condition of the UPS module.
1. Press the “Shutdown” menu button on the touchscreen. The Shutdown screen will appear in the
multipurpose window (see
).
2. Press the “UPS” button. This brings up a warning that pressing “OK” will shut off the UPS and
transfer the load to bypass, if available (see
).
3. Press “OK” to shut down the UPS.
Figure 44 N+1 Shutdown menu commands
NOTE
Service and maintenance work must be performed only by properly trained and qualified
personnel and in accordance with applicable regulations as well as with manufacturers’
specifications.
NOTE
This shutdown turns Off the inverter and the rectifier and trips all DC source breakers.
Transfers load to bypass, if available.