Operation
19
Liebert
®
NXL
™
2.3
Event Management
This menu item permits changing how the Liebert NXL handles Alarms, Faults and Status
information. Each event can be configured for the following:
• Latch (yes/no)—Event stays active in the event window, even if the fault condition has been
cleared, until user acknowledges it by pressing the “Reset” button.
• Audible (yes/no)—Will set Audible alarm when event occurs
• Event log (yes/no)—Will display event in Event log when it occurs
See
for a list of alarms, fault and status messages.
Figure 21 Typical Event Management Parameters
2.4
Status Reports Menu
This menu accesses the events records.
•
Event Log
—Up to 2048 time/date stamped events are captured in the log. The oldest record will
be overwritten with a new record once the buffer reaches 2048 events.
•
System Status
• Total Operating Hours—Total number hours the UPS has been operational
•
Service Reminders
—Displays when service is recommended for Air Filter, AC Filter, DC Filter,
and Fan. Also shows when the Warranty and/or Maintenance Agreement will expire.
NOTE
You must press “Save” for changes to take effect.
NOTE
The recommended service time is based on typical life expectancy of those components. These
components may need serviced earlier. Talk to your Liebert service representative for more
details.
Содержание Liebert NXL 250 kVA
Страница 8: ...vi ...
Страница 51: ...Operation 43 Liebert NXL Figure 42 1 N UPS Transfer to Inverter menu commands ...
Страница 57: ...Operation 49 Liebert NXL Figure 45 1 N UPS shutdown menu commands ...
Страница 86: ...Specifications Liebert NXL 78 ...
Страница 110: ...UPS Alarm and Status Messages Liebert NXL 102 NOTES ...
Страница 111: ......