4 Chapter 4 - Specifications
4.1 Conformity and Standards
This equipment complies with the following requirements:
Normative references:
Safety:
* EN 50178
EMC:
* EN61000-6-2 (2001-10;immunity)
* EN61100-6-3(emission)
The equipment must be installed in accordance with these instructions and used only with accessories approved by the
manufacturer to maintain conformity with the standards.
4.2 General Specifications
•
Manual and Automatic Transfers
•
Sense and transfer time – less than 6 milliseconds
•
Break-Before make switching
•
Selectable preferred source
•
Selectable auto/manual retransfer
•
In-phase transfer window – adjustable from 7.5 ± 1°
•
Convection cooling
•
Hot swappable electronic static switching module
•
Live mimic on Hot swappable unit for indicating load supply status & alarms
•
Make before break manual bypass switch to transfer load from static switch to direct source 1 or source 2
•
Isolated neutrals
4.3 Environmental specifications
ENVIRONMENTAL
CHARACTERISTICS
UNITS
DESCRIPTION
Heat dissipation
W
75
Storage temp. range
°C
-40 to 60°C
Operating temp. range
°C
0 to 40°C
Relative humidity
%
0 to 95%
Operating altitude
m
Up to 1500m (5,000 ft)
Storage / Transport Altitude
m
Up to 12000m (40,000 ft)
Audible Noise
db
< 45 db at 1.5 m
(03/04)
Page
4-1