Operating Instructions
25
Set Date/Time:
Allows user to enable/disable DST
(Daylight Saving Time), change the Day, Date and
Time setting on Nfinity. When enabled, the time will
automatically adjust to Daylight Saving Time.
Max Load Alarm Set:
Allows an alarm to set when
Nfinity’s load reaches a specific level.
UPS Shutdown Delay:
Delays UPS shutdown for
specified amount of time after receiving shutdown
command via relay contacts only.
Redundant Alarm Set:
Sets Alarm to notify user
when redundancy is no longer available.
Service Contact:
Set a contact for the user to reach
if problems occur.
Remote Shutdown:
Enables / Disables the Remote
Communications Shutdown.
If you are using MultiLink™ software, this parameter
should be enabled in order for the UPS output to be
turned off once the operating system has been shut-
down.
External Battery:
Sets total amp-hour for external
batteries to provide a more accurate runtime remain-
ing value on the LCD display and through communi-
cations.
When using the Non-Modular External Battery
Cabinets with Chargers (P/N: PB10SLF105WC120),
enter the following:
Set Time/Date
DST Mode
Set Time/Date
DST Mode
DST Mode
Enabled
* Disabled
Set Date/Time
Date/Time
MM/DD/YYYY
HH:MM:SS
Max Load Alarm Set
Mode
Threshold
Alarm Mode
Max Load Alarm Mode
* Enable
Disable
Threshold
Max Load Alarm Set
Threshold kVA = xx.x
UPS Shutdown Delay
xxx seconds
Redundant PWR Alarm Set
Enable
* Disable
# Cabinets
AH Value
Charge Current
1
0091
07.0
2
0182
14.0
3
0273
21.0
4
0364
28.0
5
0455
35.0
6
0546
42.0
Service Contact
>Company Name
Company Phone
Company Name
Company/Name
LIEBERT CORP.
Phone Number
Phone Number
WWW.LIEBERT.COM
Remote Shutdn
* Enable
Disable
External Battery
Amp-hour
> Charge Current
External Batt Config
Enter total amp-hour
0000
External Batt Config
Enter charge current
00.0