Installation
Liebert
®
IntelliSlot
™
Unity
™
Card User Manual
8
4. Connect an Ethernet cable to the card’s Ethernet RJ-45 port for IP communication interfaces.
5. Connect a serial cable to the card’s 485 RJ-45 port for RS-485 communication interfaces (see
Connect an RS-485 Serial Cable
2.1.1
Assigning the Card’s IP Address
2.1.1.1 DHCP
The Liebert IntelliSlot Unity card is factory-configured for DHCP. If a Static or BootP network configuration
is required, change the Boot Mode as described in
. Connect an RJ-45 cable to the
card and it will receive an IP address from the DHCP server. Contact the DHCP administrator to obtain the
IP address using the Liebert IntelliSlot Unity card’s MAC address. The MAC address is printed on the
card’s faceplate.
If the DHCP administrator is not available or there is no way of
determining the IP address assigned by the DHCP server, use a
computer with a direct Ethernet connection to the Liebert IntelliSlot
Unity card, and the Autoconfiguration IPv4 Address convention
described in
2.1.2 - Connect an Ethernet Cable
to access the card’s
Web page and configure the card. To see the card’s last DHCP-
assigned IP address, click the
Communications
tab, then on the left
side menu select
Support
>
Active Networking
. The table of
information will show the last IP address assigned by the DHCP
server. The card may retain that IP address when it reconnects to the
DHCP network because most DHCP systems reuse the same IP
address for the same device.
2.1.1.2 Static IP
To assign a static IP address, use the Ethernet connection to configure the card. Proceed to
and
2.2 - Change User Names and Passwords Immediately
Activity
Link
485
IS-UNITY-DP
Last
DHCP
Address
Support>Active
Networking
Communications
Tab
Содержание Liebert Intellislot Unity Card
Страница 1: ...Liebert IntelliSlot Unity Card User Manual Web SNMP Modbus BACnet YDN23 ...
Страница 2: ......
Страница 6: ...Liebert IntelliSlot Unity Card User Manual iv Page intentionally left blank ...
Страница 8: ...Liebert IntelliSlot Unity Card User Manual vi Page intentionally left blank ...
Страница 10: ...Liebert IntelliSlot Unity Card User Manual viii Page intentionally left blank ...
Страница 12: ...Important Safety Instructions Liebert IntelliSlot Unity Card User Manual 2 Page intentionally left blank ...
Страница 16: ...Introduction Liebert IntelliSlot Unity Card User Manual 6 Page intentionally left blank ...
Страница 38: ...Enable Communication Protocols Liebert IntelliSlot Unity Card User Manual 28 Page intentionally left blank ...
Страница 88: ...Firmware Updates Liebert IntelliSlot Unity Card User Manual 78 Page intentionally left blank ...
Страница 91: ......