5.3 Terminal Block Communication
The Terminal Block includes eight pins, as shown in
Figure 5-1 Terminal-block communication pin layout
5.3.1
Any Mode Shutdown
The purpose of Any Mode Shutdown is to shut down the UPS output by turning Off the rectifier, inverter
and static switch so that there is no power to the loads.
Any Mode Shutdown can be operated locally or remotely:
• Local Any Mode Shutdown can be performed by shorting pins1 and 2.
• Remote Any Mode Shutdown can be performed using a switch mounted at a remote location and
connected to pins1 and 2.
No.
Description
1
Low battery warning
2
On-battery warning
3
Any mode shutdown
4
Battery mode shutdown
NOTE
Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown,
depending on the settings in the configuration program.
A current-limited source for this optocoupler (+12 VDC, 50 mA) will be available from the UPS.
The connection to the UPS for remote connection will be via terminal block connector.
Any Mode Shutdown wiring must conform to all national, regional and local wiring regulations.
!
WARNING
When the Auto-Enable output option is selected and the UPS output is disabled using Any Mode
Shutdown, the Liebert GXT4’s output can turn On automatically and without warning if the
connection is changed.
Содержание Liebert GXT4-10000RT230
Страница 1: ...Liebert GXT4 UPS 230 V 5000 VA 10 000 VA User Manual ...
Страница 2: ......
Страница 44: ...Operation and Display Panel Liebert GXT4 User Manual 36 Page intentionally left blank ...
Страница 52: ...Communication Liebert GXT4 User Manual 44 Page intentionally left blank ...
Страница 60: ...Troubleshooting Liebert GXT4 User Manual 52 Page intentionally left blank ...
Страница 67: ......