26
Alarm
type
Code
Icon
Possible cause
Remedy
Fault
01
The internal converter failed, so the
DC bus voltage could not be
boosted correctly.
Contact the dealer for repair
Fault
02
1) The mains input or load
transient current cause the DC
bus voltage too high.
2) The internal converter failed.
1) Shut down and restart the UPS to
see if it happens again. If the
problem
still
persists,
please
contact the dealer for repair.
2) Contact the dealer for repair.
Fault
03
The internal converter fails, so the
DC bus voltage is too low.
Contact the dealer for repair.
Fault
04
1) The load is special or abnormal,
so the internal positive and
negative DC bus voltages are
unbalanced;
2) The internal converter failed.
Contact the dealer.
Fault
11
The internal inverter fails, so the
inverter voltage could not start up
correctly.
Contact the dealer for repair.
Fault
12
The internal inverter fails, so the
inverter voltage is too high.
Contact the dealer for repair.
Fault
13
The internal inverter fails, so the
inverter voltage is too low.
Contact the dealer for repair.
Fault
14
Short circuit occurs on the UPS
output.
Remove short circuited output/situation.
If the problem still persists, please
contact the dealer for repair.
Fault
1A
UPS output power is negative. It
means there is energy feedback
into the internal of UPS from output.
It may be caused by regenerative
load or the current control failure in
the parallel system.
Contact the dealer.
Fault
21
The internal battery SCR failed and
short circuited.
Contact the dealer for repair.
Fault
2A
Short circuit occurs on the charger
output.
Remove
short
circuited
output/situation. If the problem still
persists, please contact the dealer for
repair.
Fault
24
The internal inverter relay is stick to
short circuited or the SCR of STS
(Static
Transfer
Switch)
is
short-circuited.
Contact the dealer for repair.
Fault
41
The internal temperature is too high
and
reaches
the
fault
level
(shutdown point):
1) Maybe the environment is hot.
2) Maybe the fan is blocked or
failed.
3) Maybe the ventilation is blocked
by the wall or other goods.
4) Overload
1) Make
sure
the
ambient
temperature not over 40
º
C;
2) Make sure the fan is OK;
3) Make sure the ventilation is well;
4) Remove some loads if possible.
Fault
42
Internal communication between
the CPUs failed
Contact the dealer for repair.
Fault
43
Overload times are out of the
specification and the UPS shuts
down automatically.
Remove excess loads from UPS
output and restart it.