Electrical Connections
61
Liebert
®
CRV
™
9.1.3 Standard Electrical Field Connections—300mm (12") DX Models
Source: DPN002810, Rev. 2
1.
High-Voltage Connection Through the Rear of the Switch Box—
1-1/8" (28.6mm) and
1-3/4" (44.5mm) diameter concentric knockout.
2.
Low-Voltage Connection Through the Bottom of the Unit—
Quantity of two 7/8" (22mm)
diameter knockouts, not shown; see
3.
High-Voltage Connection Through the Top of the Unit—
1-1/4" (32mm) and 1-3/4" (44.5mm)
diameter concentric knockout, not shown; see
.
4.
Low-Voltage Connection Through the Top of the Unit—
Two knockouts, 7/8" (22mm)
.
5.
Three-Phase Electrical Service—
Connect to terminals on disconnect switch. Three-phase
service not by Emerson. (Refer to serial tag for total unit full load amps, wire size amps and
maximum overcurrent protective device size.
6. Factory-Installed Locking Disconnect Switch
7.
Earth Ground—
Terminal for field-supplied earth grounding wire.
8.
Remote Unit Shutdown—
Replace existing jumper between Terminals 37 and 38 with
field-supplied normally closed switch having a minimum 75VA, 24VAC rating. Use field-supplied
Class 1 wiring.
9.
Customer Alarm Inputs
—Terminals for field-supplied, normally closed contacts, having a
minimum 75VA, 24VAC rating, between Terminals 3 and 50, 2 and 51, 5 and 55 or 3 and 56. Use
field-supplied Class 1 wiring. Terminals 5 and 55 not available when optional Condensate Pump
is installed.
10. )
Common Alarm—
On any alarm, normally open dry contact is closed across Terminals 75 and
76 for remote indication. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring.
11.
Heat Rejection Interlock—
On any call for compressor operation, normally open dry contact is
closed across Terminals 70 and 71 to heat rejection equipment. 1A, 24VAC maximum load. Use
field-supplied Class 1 wiring.
12.
CANbus Connector—
Terminal block with Terminals 49-1 (CAN-H) and 49-3 (CAN-L) + SH
(shield connection). The terminals are used to connect the CANbus communication cable (field
supplied) from the indoor unit to the Liebert MC Condenser-Premium Model.
CANbus Cable—
CANbus cable provided by others to connect to the outdoor condenser. Cable
must have the following specifications:
a. Conductors
—
22-18AWG stranded, tinned copper
b. Twisted pair (minimum eight twists per foot [305mm])
c. Braided shield or foil shield with drain wire
d. Low capacitance
—
15pf/ft or less
e. UL-approved temperature rated to 167°F (75°C)
f. UL-approved voltage rated to 300V
g. UV- and moisture-resistant if not provided in conduit
h. Plenum rated
—
NEC type CMP (if required by national or local codes)
9.1.4 Electrical Field Connections for Optional Features—300mm (12") DX Models
Source: DPN002810, Rev. 2
13.
Condensate Pump High Water Alarm
(available when optional pump is installed)—On pump
high water indication, normally open dry contact is closed across Terminals 88 and 89 for remote
indication. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring.
14.
Liebert Liqui-tect
®
Shutdown and Dry Contact
(available when optional Liebert Liqui-tect
sensor is installed)—On Liebert Liqui-tect activation, normally open dry contact is closed across
Terminals 58 and 59 for remote indication. The Liebert Liqui-tect sensor notifies Liebert iCOM
®
of indication through Terminals 60 and 61. 1A, 24VAC maximum load. Use field-supplied Class 1
wiring.
15.
Additional Common Alarm
—On any alarm, one additional normally open dry contact is closed
across Terminals 94 and 95 for remote indication. 1A, 24VAC maximum load. Use field-supplied
Class 1 wiring.