Maintenance
Liebert
®
CRV
™
164
16.6 Inspect and Replace the Air Filters—600mm (24") Models
Check the air filter monthly to maintain efficient air distribution through the evaporator coil.
1. Switch Off the CRV.
2. Open the rear panel by rotating the three locks with a screwdriver.
3. Wait until the fans stop rotating. When you open the first lock, you also open a safety switch that
cuts the input power; see
below.
Figure 136 Air filter location and input power safety switch—600mm (24") models
To extract the filters (refer to
:
1. Push up the upper filter.
2. Pull the bottom of the filter away from the Liebert CRV.
3. Pull it out of the unit.
4. Lift the lower filter up
5. Pull the bottom of the filter away from the Liebert CRV.
6. Pull it out of the unit.
!
WARNING
Risk of contact with high speed rotating fan blades. Can cause serious injury or death.
Open all local and remote electric power disconnect switches, verify with a voltmeter that
power is Off and verify that the fan blades have stopped rotating before opening the cabinet
door.
Safety
Switches
Safety Switch
Air Filter