54 Chapter 7 Dual Bus System
Liebert APM 90 Integrated Modular UPS User Manual
7.1.4
LBS Cable
For APM-to-APM dual bus system, connect the optional LBS cables (5m, 10m and 15m selectable) between
the two UPSs as shown in Figure 7-2 to Figure 7-3. The J3 and J4 ports are provided on the front panel of the
bypass module, as shown in Figure 7-2.
Note
You must use the shortest LBS cable to suit the application and must not coil excess. Meanwhile, separate the LBS cable
from the power cables to prevent electrical inteferences.
UPS 1
Bypass module
LBS cable
J2
J3
J4
J2
J3
J4
Bypass module
UPS 2
UPS 1
UPS 2
Bypass module
Bypass module
J2
J2
J3
J3
J4
J4
LBS cable
Figure 7-2
Connection of typical dual bus system of two single UPSs without redundancy LBS cable
UPS 1
Bypass module
LBS ca
ble
J2
J3
J4
J2
J3
J4
Bypass module
UPS 2
LBS
cab
le
UPS 1
UPS 2
Bypass module
Bypass module
J2
J2
J3
J3
J4
J4
LBS
cab
le
LBS ca
ble
Figure 7-3
Connection of typical dual bus system of two single UPSs with redundancy LBS cable