6 Chapter 2 Installation
Note
1. If the condenser is to be placed horizontally, you should complete the installation of legs while the condenser is located
vertically.
2. When moving the condenser by hand, to avoid distortion and system leakage, do not touch the copper pipes.
Inspection
After the product arrival, you should check the accessories against the packing list. If any parts are found missing or
damaged, please report to the carrier immediately. If any covert damage is found, please report to the carrier and the
distributor immediately.
2.2 Installation Notes
The installation notes of the condenser are as follows:
1. To ensure the heat dissipation capacity, install the condenser in the place with smooth airflow. Do not install it where
the coil of the condenser may be obstructed by dust or snow. Ensure that there is no steam or waste heat around.
2. If possible, the horizontal installation is recommended to reduce the noise.
3. The condenser should be installed away from the residential areas (
≥
15m).
4. Be careful not to damage the waterproof layer and observe the local regulations when the condenser is installed on
the roof of the building.
5. Position the condenser higher than the indoor unit to ensure normal oil return.
6. Follow the installation arrows on the condenser for correct installation direction.
2.3 Space Requirements
Note
1. A 4000mm clearance is required around the condenser air outlet.
2. 600mm service spaces are required on the four sides of the condenser.
The condenser needs sufficient installation and service space around the installation place. The specific space
requirements are shown in Figure 2-3 and Figure 2-4.
450
Airflow
1200
Airflow
600
Figure 2-3 Horizontal installation space requirement (unit: mm)
4000
600
Airflow
Figure 2-4 Vertical installation space requirement (unit: mm)
Liebert.PEX Condenser User Manual