background image

10

Keystone

 OM11 - EPI2 DEvIcENEt INtErfacE

InstallatIon and maIntenance InstructIons

Indication

description

data type

range

e.u.

fully open

the fully Open indication is set to 1 when the actuator is at fully Open position. this indication 
reflects the status of the open limit on the actuator.

Boolean

0-1

-

Opening

the Opening indication is set to 1 when the actuator is moving toward opening direction.

Boolean

0-1

-

closing

the closing indication is set to 1 when the actuator is moving toward closing direction.

Boolean

0-1

-

actuator moving

this indication is set to 1 when the actuator is moving either in opening or in closing direction.

Boolean

0-1

-

fully close

the fully close indication is set to 1 when the actuator is at fully close position. this indication 
reflects the status of the close limit on the actuator.

Boolean

0-1

-

Motor stopped

this indication is set to 1 when the actuator is not moving and the motor has stopped.

Boolean

0-1

-

Intermediate 
position

this indication is set to 1 when the valve is at an intermediate position.

Boolean

0-1

-

Positioner active

this indication is set to 1 when the on-board positioner is enabled.

Boolean

0-1

-

alarm in open 
direction

Open command not available due to current alarm trip in open direction. the diagnostic indication is 
cleared when the alarm that has generated the fault disappears.

Boolean

0-1

-

alarm in close 
direction

close command not available due to current alarm trip in close direction. the diagnostic indication is 
cleared when the alarm that has generated the fault disappears.

Boolean

0-1

-

general alarm

Bus can only read data due to alarm present. the diagnostic indication is cleared when all the alarm 
conditions are cleared.

Boolean

0-1

-

LOcaL selected

No operation from bus because LOcaL selector switch is activated. the diagnostic indication is 
cleared when the selector is turned to rEMOtE.

Boolean

0-1

-

HardWired mode 
selected

No operation from bus because HarDWIrED mode is activated. the diagnostic indication is cleared 
when the input HW MODE is not powered.

Boolean

0-1

-

PDa active

No operation from bus because PDa operator interface has the control (only if Bluetooth option is 
available). the diagnostic indication is cleared when the PDa control is released.

Boolean

0-1

-

Monitor relay

this indication is set to 1 when the actuator is available for bus control. Monitor relay indication 
means that the local selector is at remote position, no other remote interfaces have the control 
(Hardwired or PDa) and no alarms are present.

Boolean

0-1

-

Power failure 
alarm

this bit is set when the main power supply is not in the proper range. the diagnostic indication is 
cleared at the next power up if the power supply is corrected.

Boolean

0-1

-

torque alarm in 
opening

this bit is set when the torque has reached the programmed limit while the actuator was moving in 
opening direction. the diagnostic indication is cleared by a close command

Boolean

0-1

-

torque alarm in 
closing

this bit is set when the torque has reached the programmed limit while the actuator was moving in 
closing direction. the diagnostic indication is cleared by an Open command.

Boolean

0-1

-

Stroke limit alarm

this bit is set when the current position is behind the Open or close limit switches or as result of an 
incorrect torque Set. the diagnostic indication is cleared when the position returns within the limits 
or after a successful torque Set procedure

Boolean

0-1

-

Local control alarm this bit is set when the optional Local control Module does not work correctly. the diagnostic 

indication is cleared when the Local control works without problems.

Boolean

0-1

-

Motor direction 
alarm

this bit is set when the motor drive has recognized an incorrect behaviour. the diagnostic indication 
is cleared by a command in the opposite direction.

Boolean

0-1

-

Jammed valve

this bit is set when the actuator detects a jammed valve condition. the diagnostic indication is 
cleared by any new command.

Boolean

0-1

-

HW alarm

this bit is set when the actuator detects a general hardware error. the diagnostic indication is 
cleared at the next power up under normal condition.

Boolean

0-1

-

Position sensor 
alarm

this bit is set when the actuator detects that position sensor is not working properly.

Boolean

0-1

-

High temperature 
alarm

this bit is set when the internal temperature is out of the operational limits. the diagnostic indication 
is cleared when the internal is within the limits.

Boolean

0-1

-

current position

the current position read from base card

Integer

0-1000

0.1%

current torque

the current torque read from base card

Integer

0-100

%

Internal 
temperature

the current internal temperature

Integer

-45 +85

°c

Содержание Keystone OM11

Страница 1: ...ored in the same environment of the actuator Warning The electronic parts of the EPI2 actuators and all option modules can be damaged by a discharge of static electricity Before you start touch a grounded metal surface to discharge any static electricity Warning EPI2 actuators must be electrically isolated before any disassembling or reassembling operations Before any disassembling or reassembling...

Страница 2: ...intenance instructions Figure 1 Label for NON US MARKET Digits X7X8 on product coding chart Figure 2 Label for US MARKET Digit 6 on product coding chart Figure 3 Example of F02 old version heatsink present Figure 4 Example of F02 new version heatsink no present ...

Страница 3: ...bly and for setting the actuator controls With an Allen wrench of 5 mm unscrew the cover screws Figure 5 Figure 5 Figure 6 Figure 7 Figure 8 Remove the actuator cover Figure 6 Follow one of the following assembling procedures depending on actuator model 4 1 Assembling procedure for models 63 125 Nm old version US or NO US market Detect the black cable required for the OM11 which is already include...

Страница 4: ...ure 11 Figure 12 Figure 13 Unscrew the 3 screws Figure 9 3 pcs M3x10 Tighten the 3 metal spacers Figure 10 Connect the 8 pins connector to connector on OM11 Figure 13 Connect OM11 flat cable to connector J8 on the logic board Figure 11 Place the OM11 card onto the spacer and tighten the 4 screws Figure 12 ...

Страница 5: ...e required for the OM11 which is already included in the basic actuator disassemble local mechanical indicator Figure 14 Connect OM11 flat cable to connector on the logic board Figure 16 Connect the flat cable furnished into the kit to connector J3 on OM11 Figure 15 Place the OM11 card onto the heatsink spacers and tighten the 4 screws assemble local mechanical indicator Figure 17 Connect the 8 pi...

Страница 6: ...k to power the transceiver 29 mA at 24 V 27 mA at 17 V 25 mA at 11 V Communication Predefined master slave connection explicit message and polled I O Baud rate 125 Kbps 250 Kbps 500 Kbps default 125 Kbps Network configurable or manual configurable via on board rotary BCD switch Addressing MACID 0 63 default 63 Network configurable or manual configurable via on board rotary BCD switches Temperature...

Страница 7: ...et pushbutton Local configuration On board interface for local configuration of MACID and Baud Rate By default the board is set to accept MACID and Baud Rate from the network but it is also possible to set these parameters by hardware setting Detailed procedures are given in chapter 9 Local settings 6 2 Wiring diagram The Devicenet interface is connected to the actuator terminal board by internal ...

Страница 8: ...able data rate of 125 k baud 250 k baud and 500 k baud Adjustable power configuration to meet individual application needs High current capability up to 8 A at 24 V DC Operation with off the shelf power supplies Available power taps that allow the connection of several power suppliers Build in overload protection Controller Area Network CAN technology for Media Access Control and Physical Signalli...

Страница 9: ...lose Limit has been reached The close command is reset when a Stop Command is received from the bus Boolean 0 1 Stop command When this bit is set to 1 a Stop Command is issued to the actuator A Stop Command received from the bus resets both open and close commands Boolean 0 1 Positioner enable When this bit is set to 1 the on board positioner is enabled The positioner is enabled until this bit is ...

Страница 10: ...ol is released Boolean 0 1 Monitor relay This indication is set to 1 when the actuator is available for bus control Monitor Relay indication means that the local selector is at Remote position no other remote interfaces have the control Hardwired or PDA and no alarms are present Boolean 0 1 Power failure alarm This bit is set when the main power supply is not in the proper range The diagnostic ind...

Страница 11: ...l Delay before to initiate the safety action R W Integer 0 10 4 sec 8 4 Dead band configuration The Dead Band indicates the maximum allowed deviation from the valve position and the requested position If the deviation is bigger an open or close control command will be generated Indication Description Direction Data type Range Default E U Parameter 4 Class 100 Instance 1 Attribute 103 Dead band Thi...

Страница 12: ...ion necessary to the device configuration and to the access and alter the configurable parameters of the EPI2 actuator Indication Description Direction Data type Range Default E U Parameter 17 Class 3 Instance 1 Attribute 1 MACID The MACID to assign to the device R W Unsigned 0 63 63 Parameter 18 Class 3 Instance 1 Attribute 2 Baud rate The Baud Rate to assign to the device R W Unsigned 0 2 0 Keys...

Страница 13: ...utton ENA_CFG switch MSB LSB Address BCD Rotary switches When the DeviceNet Interface tries to set opening closing speeds actuator logic sets values in function of following table Note New version of F02 EPI2 has only the opening closing torque 2 5 and 9 see VCIOM02819 EN Note Input data Torque has different meaning in function of old and new F02 EPI2 models In particular in old F02 EPI2 models it...

Страница 14: ...ered in Configuration Mode Set the new Data Rate on the rotary switches DATA_ Press the pushbutton ENTER to confirm the new set if the new MACID is correct the CFG_OK LED turns ON Move the dip switch ENA_CFG on the OFF position to exit from Configuration Mode the DeviceNet interface module is reset to activate the new setting 9 3 DeviceNet communication speed configuration The DeviceNet interface ...

Страница 15: ... Figure 19 to choose the correct mechanical parts Table 3 EPI2 F02 cross reference table NON US MARKET Actuator model OLD 63 125 OLD 250 2K NEW 63 125 NEW 250 2K Product coding chart digit X7X8 1 phase UV VU UV VU LV HV LV HV Product coding chart digit X7X8 3 phase 31 32 33 31 32 33 3A 3B 3C 3A 3B 3C A 1 11 11 4 8 5 8 B 2 12 12 1 11 6 9 C 3 13 13 2 12 7 10 D 14 14 15 Table 4 EPI2 F02 cross referen...

Отзывы: