IE Series
Page: 2
Installation
1. Turn off all power supplying this equipment before working on or inside equipment.
2. Confirm that the unit has the same voltage rating and configuration as the power system voltage and
power system voltage to which it will be connected.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•
Confirm that the Surge Protective Device voltage rating on the module or nameplate label is not less than the
operating voltage.
Failure to follow these instructions will result in death or serious injury.
3. Install the unit and cables as close as possible to the protected equipment and secure.
4. Connect the supply cables to the line side of the device.
5. Complete the circuit by connecting cables from the load of the device to the protected equipment.
Note:
A dry contact connection is available.
6. Check that all connections are secure. Remove all tools and discarded hardware from the unit.
7. Replace the barrier, cover/door and/or trim to the equipment.
8. Equipment may be re-energized after all the above steps are complete.
Table 1: Ratings
Service Voltage
MCOV
Continuous
Current
Normal
Discharge
Current
Fusing Circuit
Breaker Size
Certification
Catalog
Numbers
120 V, 50/60 Hz,
1-phase
2 wire + ground
150 V
(L–N)
3 A
3 kA
25 A Class CC
Fuse
UL1449 /
UL1283 CSA
C22.2 No.
269.5
IE103
5 A
IE105
10 A
IE110
20 A
IE120
240 V, 50/60 Hz,
1-phase
2 wire + ground
275 V
(L–N)
3 A
IE203
5 A
IE205
10 A
IE210
20 A
IE220