background image

PACMotion VFD Input/Output Chokes Installation Guide 

Section 2 

GFK-3185A 

August 2020 

 

Input Line Chokes 

Part Number 

VFD 

Size 

Connection 

(mm

2

(mm) 

(mm) 

(mm) 

N1 

(mm) 

N2 

(mm) 

ØD 

(mm) 

Rated 

Volts 

Rated 
Amps 

Inductance 

(mH) 

Weight 

(kg) 

IC866-ICH-006-

603-20 

2.5 

95 

107 

56 

56 

43 

4.8 x 9 

500 

Max 

4.8 

1.3 

IC866-ICH-010-

603-20 

2.5 

125 

127 

71 

100 

55 

5 x 8 

10 

2.9 

2.5 

IC866-ICH-036-

603-20

 

10 

190 

205 

82 

170 

58 

8 x 12 

36 

0.81 

7.2 

IC866-ICH-050-

603-20 

16 

190 

220 

102 

170 

78 

8 x 12 

50 

0.58 

8.7 

IC866-ICH-090-

603-20 

35 

240 

280 

107 

185 

85 

10 x 

18 

90 

0.32 

16 

 

 

Figure 3: IC866-ICH-006-603-20, IC866-ICH-010-603-20 

 

Figure 4: IC866-ICH-036-603-20, IC866-ICH-050-603-20, 
IC866-ICH-090-603-20 

 

 

Part Number 

VFD 
Size 

Connection 

D2 (mm) 

(mm) 

(mm) 

(mm) 

N1 

(mm) 

N2 

(mm) 

ØD 

(mm) 

Rated 

Volts 

Rated 
Amps 

Inductance 

(

μ

H) 

Weight 

(kg) 

IC866-ICH-

200-603-00

 

310 

260 

180 

224 

117 

10 x 18 

500 

200 

73.5 

35 

IC866-ICH-

300-603-00 

370 

310 

180 

248 

139 

10 x 18 

300 

49.0 

48 

 

 

Figure 5: IC866-ICH-200-603-00 

 

Figure 6: IC866-ICH-300-603-00 

 

 

 

Содержание IC866-ICH-006-603-20

Страница 1: ...Installation Guide GFK 3185A August 2020 PACMotion VFD Input Output Chokes IP20 and IP66 Versions INSTALLATION GUIDE ...

Страница 2: ...hokes 2 2 1 Using Input Chokes 2 2 2 Dimensions IP20 Single Phase Versions 2 2 3 Mounting Dimensions IP66 Versions 4 2 4 Installation Schematic Diagram 4 Section 3 Output Line Chokes 5 3 1 Using Output Chokes 5 3 2 Dimensions Open Type 5 3 3 Mounting Dimensions Enclosed Versions 6 3 4 Installation Schematic Diagram 6 General Contact Information 7 Technical Support 7 ...

Страница 3: ...ngency to be met during installation operation and maintenance The information is supplied for informational purposes only and Emerson makes no warranty as to the accuracy of the information included herein Changes modifications and or improvements to equipment and specifications are made periodically and these changes may or may not be reflected herein It is understood that Emerson may make chang...

Страница 4: ...t the terminals and within the drive for up to 10 minutes after the disconnection of the electrical supply Wait until 10 minutes have elapsed after turning off the power supply before disconnecting the plug that supplies power to the drive It is the responsibility of the installer to ensure that the equipment or system into which the product is incorporated complies with the EMC legislation of the...

Страница 5: ...overhead cranes On all installations where the supply impedance is low or the fault current is very high On all installations where the incoming power supply is prone to spikes dips notches or other disturbances Typically the input choke will provide a significant reduction in harmonic distortion on the incoming power supply and will reduce the overall current into the drive cover and back pages 2...

Страница 6: ... 170 58 8 x 12 36 0 81 7 2 IC866 ICH 050 603 20 4 16 190 220 102 170 78 8 x 12 50 0 58 8 7 IC866 ICH 090 603 20 5 35 240 280 107 185 85 10 x 18 90 0 32 16 Figure 3 IC866 ICH 006 603 20 IC866 ICH 010 603 20 Figure 4 IC866 ICH 036 603 20 IC866 ICH 050 603 20 IC866 ICH 090 603 20 Part Number VFD Size Connection D2 mm L mm H mm B mm N1 mm N2 mm ØD mm Rated Volts Rated Amps Inductance μH Weight kg IC86...

Страница 7: ...4 82 70 70 70 58 6 151 60 85 230 Max 16 1 83 1 0 IC866 ICH 025 201 60 2 10 90 75 84 84 72 6 151 60 85 25 1 17 1 3 IC866 ICH 006 603 60 1 2 5 115 88 74 80 60 5 5 x 7 151 60 85 600 Max 6 4 8 1 6 IC866 ICH 010 603 60 2 2 5 175 137 99 130 79 5 5 x 12 151 60 85 10 3 86 3 5 IC866 ICH 018 603 60 3 10 175 137 114 130 94 5 5 x 12 151 60 85 18 2 04 7 Figure 7 Dimensions of Enclosed Versions 2 4 Installation...

Страница 8: ...motor cable length exceeds the maximum permissible motor cable length stated for the product in the relevant user manual o Specified cable lengths apply to standard type copper shielded cable only o For unshielded cables the maximum length may increase by 50 o Using a choke allows the maximum cable length to increase by 100 High capacitance motor cable is used e g typically fire resistant cables 3...

Страница 9: ... L1 mm H1 mm B1 mm Rated Volts Rated Amps Inductance mH Weight kg IC866 OCH 008 603 60 1 2 5 115 85 74 80 60 5 5 x 7 151 60 85 600 Max 8 2 0 1 7 IC866 OCH 012 603 60 2 2 5 140 110 87 100 70 5 5 x 12 151 60 85 12 1 2 3 2 IC866 OCH 018 603 60 3 10 140 110 87 100 70 5 5 x 12 151 60 85 18 0 9 3 2 Figure 12 Mounting Dimensions Enclosed Versions 3 4 Installation Schematic Diagram Figure 13 Installation ...

Страница 10: ...turns customercare cn mas emerson com Technical Support support mas apac emerson com Any escalation request should be sent to mas sfdcescalation emerson com Note If the product is purchased through an Authorized Channel Partner please contact the seller directly for any support Emerson reserves the right to modify or improve the designs or specifications of the products mentioned in this manual at...

Отзывы: