FloBoss 107 Instruction Manual
4-18
Inputs and Outputs
Revised June-2017
16.
Using ROCLINK 800 software, you can configure the module as
latched, toggled, momentary, or Timed Duration Outputs (TDO).
The discrete output channel is a normally open contact. The discrete
output is a relay switch enabled by individual signals from the processor
I/O lines and capable of handling 30 Volts dc at 1.0 A maximum.
Additionally, one DOR channel makes the normally closed contact
available to the field.
You configure the DOR so that it either retains the last value on reset or
sets to a user-specified fail-safe value. When a request is made to change
the state of a DO, the request is immediately sent to the DO.
If the DO is in momentary or toggle mode, you can enter a minimum
time-on of 50 milliseconds (.05 seconds).
Note
:
When using the discrete output to drive an inductive load (such as
a relay coil), place a suppression diode across the load. This
protects the DO from the reverse Electro-Motive Force (EMF)
spike generated when the inductive load is switched off.
4.11.1 Wiring the Discrete Output Relays
The terminals for connecting the DO wiring are shown in
Figures 4-15
and
4-16
.
Caution
You can induce ground loops by tying commons from various modules
together.
SWITCHED
DEVICE
SUPPLY
POWER
DO2-DO6
HIGH SIDE SWITCH
Figure 4-15. Discrete Output Relay Module Wiring (High Side Switch)