Emerson fisher VBL Скачать руководство пользователя страница 3

Instruction Manual

D103317X012

VBL Volume Booster

May 2017

3

Table 1. Specifications

Input Signal

Positioner output

Maximum Input Signal Pressure

(1)

VBL-1 and VBL-3

: 5.5 bar (80 psig)

VBL-2 and VBL-4: 

10.3 bar (150 psig)

Input to Output Pressure Ratio

Fixed at 1 to 1

Supply Pressure Ranges

(1)

When used in conjunction with a positioner or other
pneumatic accessory, always pipe the positioner and
booster with one common supply through a Fisher
67D, 67DR, or 95H regulator (see figure 4). A
high‐capacity filter, such as the Fisher 262K, should
be installed in the supply line to the regulator. Supply
pressure also must not exceed the maximum
pressure rating of the actuator.

Operative Temperature Limits

(1)

-40 to 93

_

C (-40 to 200

_

F)

Maximum Flow Coefficients

See table 2

Connections

Input Signal:

 1/4 NPT

Supply and Output Signal:

 1/2 NPT

Hazardous Area Classification

Complies with the requirements of ATEX Group II
Category 2 Gas and Dust

Approximate Weight

Aluminum Body:

 1.0 kg (2.2 pounds)

Declaration of SEP

Fisher Controls International LLC declares this
product to be in compliance with Article 4 paragraph
3 of the PED Directive 2014/68/EU. It was designed
and manufactured in accordance with Sound
Engineering Practice (SEP) and cannot bear the CE
marking related to PED compliance.

However, the product 

may

 bear the CE marking to

indicate compliance with 

other 

applicable European

Community Directives.

NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 -

 

Process Instrument Terminology.

1. The pressure/temperature limits in this document, and any applicable code or standard limitation should not be exceeded.

Table 2. Maximum Flow Coefficients

Instrument

Supply Port Coefficients

Exhaust Port Coefficients

C

v

C

v

VBL‐1 volume booster

2.5

1.1

VBL-2 volume booster

2.5

1.1

VBL‐3 volume booster

2.5

1.8

VBL-4 volume booster

2.5

1.8

FIELDVUE

t

 DVC6200, DVC6200 SIS, DVC6200f, DVC6200p,

DVC6000, DVC6000 SIS, DVC6000f digital valve controllers

0.37

0.31

FIELDVUE DVC2000 digital valve controller
Low pressure relay
High pressure relay

0.13
0.19

0.15
0.20

Fisher 3570 valve positioner

0.25

0.25

Fisher 3582 valve positioner

0.17

0.19

Fisher 3610J, 3610JP, 3611JP, 3620J, 3620JP, 3621JP valve positioners

0.37

0.30

Содержание fisher VBL

Страница 1: ...and and follow all of the contents of this manual including all safety cautions and warnings If you have any questions about these instructions contact your Emerson sales office or Local Business Partner before proceeding Description The VBL volume booster is used in conjunction with a positioner on a throttling control valve to increase stroking speed The booster has a fixed deadband controlled b...

Страница 2: ...ting you can install connectors and piping with the VBL volume booster The O rings and diaphragms in the VBL volume booster are HNBR Hydrogenated Nitrile HNBR demonstrates excellent temperature capability and shelf life over standard nitrile Specifications Specifications for the VBL volume booster are listed in table 1 Information for an individual unit as it comes from the factory appears on the ...

Страница 3: ... Controls International LLC declares this product to be in compliance with Article 4 paragraph 3 of the PED Directive 2014 68 EU It was designed and manufactured in accordance with Sound Engineering Practice SEP and cannot bear the CE marking related to PED compliance However the product may bear the CE marking to indicate compliance with other applicable European Community Directives NOTE Special...

Страница 4: ...essure supply However if the system is in a transient state at the time of pressure supply loss or if changes to the booster s input signal are sufficient to overcome the deadband the booster will exhaust A loss of a pressure supply either separate or common to a Fisher 3582 or 3610J positioner will cause the positioners output pressure booster s input pressure to decay Always pipe the positioner ...

Страница 5: ...or typical applications are shown in figures 4 and 5 Ensure that the piping is of proper size to meet the capacity demands of the booster and that you equip the actuator with properly sized input connections Supply Pressure Supply pressure must be filtered clean dry air or noncorrosive gas WARNING If a flammable or hazardous gas is to be used as the supply pressure medium personal injury property ...

Страница 6: ... screw figure 3 four or five turns counterclockwise from the fully closed position With the actuator in operation slowly turn the restriction clockwise until the booster operates in response to large changes in the input signal yet allows small changes to move the actuator without initiating booster operation Figure 3 Volume Booster Sectional View GE26237 Section UPPER DIAPHRAGM DIAPHRAGM PLATE AS...

Страница 7: ...ired to reduce the pressure differential The port remains open until the difference between the booster input and output pressures returns to within the deadband limits of the booster With the bypass restriction adjusted for stable operation signals having small magnitude and rate changes pass through the bypass restriction and into the actuator without initiating booster operation Both the supply...

Страница 8: ... be construed as warranties or guarantees express or implied regarding the products or services described herein or their use or applicability All sales are governed by our terms and conditions which are available upon request We reserve the right to modify or improve the designs or specifications of such products at any time without notice E 2010 2017 Fisher Controls International LLC All rights ...