Emerson Fisher Snappy Joe N550 Скачать руководство пользователя страница 5

5

CAUTION

Possible hand and finger pinch point    

between closing Type N550 handle and 

latch block.  Handle closes quickly and 

with extreme force.  Keep hands and 

fingers away from handle as it closes.    

  15.  Test the remote release and Type N550 operation 

from the most remote location.  Rotate handle 

counterclockwise to open valve.  Valve must stay 

open.  HANDLE AND VALVE MUST QUICKLY 

“SNAP” CLOSED when (a) the remote release 

cable is pulled, and (b) handle is pushed closed 

from the open position.    

!

WARNING

All open Type N550 emergency valve(s)   

attached to the remote release must  

 

properly close when the release cable 

is pulled.  

Pneumatic Hook-Up  

 

Type P327D Pneumatic Release  

Block Installation   

If several valves are installed at the same location, remote 

release may be accomplished with the Type P327D   

pneumatic release block which replaces the cable latch 

block installed on the Type N550 valves.    
To install the Type P327D, see Figure 4:  

 

  1.  Close the Type N550 valve.  Handle is parallel to 

       the pipe. 
  2.  Remove the long end of the external spring from      

under the latch block. 

 DO NOT REMOVE                  

SPRING FROM HANDLE.    

  3.  Remove latch bolt(s).  Older valves will have 2 

bolts.  

DISCARD CABLE LATCH BLOCK.

    

  4.  Use a 5/32-inch (4 mm) Allen head wrench to           

       screw 1/4-inch (6,4 mm) long bolt into bottom hole.

  5.  Tighten until bolt head seats firmly on body.   

  6.  Place latch block on body with lower blind hole 

over bolt in body.    

  7.  Install 3/4-inch (19 mm) long bolt through 

second hole and firmly tighten with 5/32-inch 

(4 mm) Allen head wrench.   

  8.  Refasten long end of spring under latch block by   

ROTATING 180 DEGREES CLOCKWISE. 

  

  9.  Attach the remote air source to the cylinder end 

with appropriate supply tubing and valving.  A 

regulated air supply of 

30 to 70 PSIG  (2,1 to     

4,8 bar) 

to the Type P327D pneumatic release 

cylinder is required for proper operation. 

Figure 4.

  Type P327D Pneumatic Cylinder Installation

TO HOSE

NAMEPLATE

TO TANK

5/32 (4) ALLEN HEAD

WRENCH REQUIRED

AIR SOURCE – 1/8 NPT

5/32 (4) ALLEN HEAD

WRENCH REQUIRED

T40337 

INCHES 

(mm)

5

Type N550

Содержание Fisher Snappy Joe N550

Страница 1: ...ntended for in line use on LP Gas or Anhydrous Ammonia NH3 service The valves may be installed on both ends of transfer hoses where the hose connects the bulk plant piping to the bobtail transport or tank car They provide a quick way of shutting off gas flow in the event of a hose rupture and meet the requirements for such service when correctly installed with a remote release and proper piping su...

Страница 2: ...en a storage tank and the transfer hose connection at the truck or tank car loading unloading area They can be placed in a line used either for filling or withdrawing from the storage tank or both The valve shall be installed to shutoff flow from the tank towards the hose enabling the valve to control product loss in case of a hose break WARNING The Type N550 valves are spring closed aided by pres...

Страница 3: ...de enough pull on the hose connection to cause a break in the system That break must not occur between the Type N550 and the storage tank Fusible Element Location A fusible element that will close the Type N550 shall be located within five feet of the hose connection If the Type N550 is placed within five feet of the hose connection this requirement is met If not an additional fusible element must...

Страница 4: ... of the cable housing and cable housing nut fit into the conical end of the latch block Pulling the excess inner cable through the housing from the remote release end will hold the housing in the latch block 10 Mount the remote release cylinder assembly to a suitable support at the remote release location 7 16 inch 11 mm diameter mounting hole but do not tighten the mounting nut 11 At the remote r...

Страница 5: ...e Type P327D see Figure 4 1 Close the Type N550 valve Handle is parallel to the pipe 2 Remove the long end of the external spring from under the latch block DO NOT REMOVE SPRING FROM HANDLE 3 Remove latch bolt s Older valves will have 2 bolts DISCARD CABLE LATCH BLOCK 4 Use a 5 32 inch 4 mm Allen head wrench to screw 1 4 inch 6 4 mm long bolt into bottom hole 5 Tighten until bolt head seats firmly...

Страница 6: ... connection When the hose stretches more than the amount of slack left in the cable the tightening cable will pull the lever down and close the Type N550 valve CAUTION Possible hand and finger pinch point between closing Type N550 handle and latch block Handle closes quickly and with extreme force Keep hands and fingers away from handle as it closes 10 Test the remote release and Type N550 operati...

Страница 7: ...epaired in the field However due to the special fire resistant seals and assembly techniques repairs should be done only by trained personnel If repair should become necessary contact your local LP Gas Equipment Distributor for information and assistance Only parts manufactured by Emerson Process Management Regulator Technologies Inc should be used for the repair of Fisher Type N550 Valves Be sure...

Страница 8: ...eel T12851T0012 29 Washer Carbon steel 2 Required T1207524082 30 Packing Stack T12854T0012 31 Follower 174 Stainless steel T12841T0012 32 Retainer Steel T20674T0012 33 Bolt Stainless steel 2 Required T12499T0012 34 Bushing T12551T0012 35 Washer Nylon PA T12781T0012 36 Latch Block Aluminum T13800T0012 37 Spring 302 Stainless steel T13877T0012 38 Plunger Polyester T12846T0012 39 Cable T12849T0012 40...

Отзывы: